9. Faults

Streszczenie: Konfiguracja błędów wzmacniacza: parametry błędów i ich zatrzaskiwanie (latching), kasowanie błędów zatrzaśniętych i niezatrzaśniętych, błąd i ostrzeżenie uchybu nadążania (following error) oraz okna śledzenia pozycji i prędkości (tracking window).
EN: Fault configuration: latched and non-latched faults, following error faults/warnings and tracking windows.

Dotyczy: program CME 2 do konfiguracji i strojenia serwonapędów oraz napędów krokowych Copley Controls (m.in. Xenus, Accelnet, Stepnet, Accelus, Junus)
Źródło: dokumentacja producenta (Copley Controls CME 2 User Guide); tabele przepisane z obrazów na tekst, opisy diagramów – opracowanie Multiprojekt

This chapter shows how to configure the amplifier’s fault latching. Perform the basic steps outlined below. Details follow in the chapter: 

11. image.pngButton: Configure FaultsClick Configure Faults to open Faults Configuration screen.

image.pngScreenshot: Faults – Click Configure Faults to open Faults Configuration screen


22. Select the faults to latch. See Fault Configuration Parameters
3

3. Click OK to close screen and save changes to amplifier RAM.

4image.pngButton: Save to FlashOn the Main screen, click Save to Flash to avoid losing the changes. 

DANGER:

Risk of unexpected motion with non-latched faults.faults

image.png

After the cause of a non-latched fault is corrected, the amplifier re-enables the PWM output stage without operator intervention. In this case, motion may re-start unexpectedly. Configure faults as latched unless a specific situation calls for non-latched behavior. When using non-latched faults, be sure to safeguard against unexpected motion.
Failure to heed this warning can cause equipment damage, injury, or death. 

9.1:1 Fault Configuration Parameters

Each of the following faults can be latched by selecting it on the Fault Configuration screen. For more information on latching, see Fault Latching Notes. For details on limits and ranges, see the amplifier documentation.

Note: The list of faults may vary with amplifier model.

image.pngFault Configuration Parameters

Fault

Description

Fault Occurs When…Fault is Corrected When…
*Amp Over TemperatureAmplifier’s internal temperature exceeds specified temperature.Amplifier’s internal temperature falls below specified temperature.
Motor Phasing ErrorEncoder-based phase angle does not agree with Hall switch states. This fault can occur only with brushless motors set up using sinusoidal commutation. It does not occur with resolver feedback or with Halls correction turned off.Encoder-based phase angle agrees with Hall switch states. See Trouble Shoot Manual Phase w/ Encoder and Halls.
*Feedback errorOver current condition detected on output of the internal +5 Vdc supply used to power the feedback. Resolver or analog encoder not connected or levels out of tolerance. Differential signals from incremental encoder not connected.Encoder power returns to specified voltage range. Feedback signals stay within specified levels. Differential signals connected.
*Motor Over TempMotor over-temperature switch changes state to indicate an over-temperature condition.Temperature switch changes back to normal operating state.
Under VoltageBus voltage falls below specified voltage limit.Bus voltage returns to specified voltage range.
Over VoltageBus voltage exceeds specified voltage limit.Bus voltage returns to specified voltage range.
*Following ErrorUser set following error threshold exceeded.See Position and Velocity Error Notes.
*Short Circuit DetectedOutput to output, output to ground, internal PWM bridge fault.Short circuit has been removed.
Command Input LostPWM or other command signal not present.Command signal restored.
Over Current (Latched)Output current I²T limit has been exceeded.Amplifier is reset and re-enabled.
*Latched by default.

9.2:2 Fault Latching Notes

9.2.1:1 Clearing Non-Latched Faults

The amplifier clears a non-latched fault, without operator intervention, as soon as the fault condition is corrected.

DANGER: Risk of unexpected motion with non-latched faults.

image.png

faults


After the cause of a non-latched fault is corrected, the amplifier re-enables the PWM output stage without operator intervention. In this case, motion may re-start unexpectedly. Configure faults as latched unless a specific situation calls for nonlatched behavior. When using non-latched faults, be sure to safeguard against unexpected motion.
Failure to heed this warning can cause equipment damage, injury, or death.

9.2.2:2 Clearing Latched Faults

A latched fault is cleared only after the fault has been corrected and at least one of the following actions has been taken:
•

  • Power-cycle the amplifier
    •
  • Cycle (disable and then enable) an enable input that is configured as

Enables with Clear Faults or Enables with Reset
•

  • Access the CME 2 Control Panel and press Clear Faults or Reset
    •
  • Clear the fault over the CANopen network or serial bus

9.2.3:3 Example: Non-Latched vs. Latched Faults

For example, the amplifier temperature reaches the fault temperature level and the amplifier reports the fault and disables the PWM output. Then, the amplifier temperature is brought back into operating range. If the Amp Over Temperature fault is not latched, the fault is automatically cleared and the amplifier’s PWM outputs are enabled. If the fault is latched, the fault remains active and the amplifier’s PWM outputs remain disabled until the faults are specifically cleared (as described above). 

9.3:3 Position and Velocity Error Notes

9.3.1:1 Error-Handling Methods

In position mode, any difference between the limited position output of the trajectory generator and the actual motor position is a position error. The amplifier’s position loop uses complementary methods for handling position errors: following error fault, following error warning, and a position-tracking window.

To set position error handling parameters for servo amplifiers, see Enter basic Position Loop settings. For stepper amplifiers, see Set Position Limits in Stepper Mode.

Likewise, in velocity or position mode, any difference between the limited velocity command and actual velocity is a velocity error. The amplifier’s velocity loop uses a velocity tracking window method to handle velocity errors. (There is no velocity error fault.)

To set parameters for velocity error handling, see Enter basic Velocity Loop settings

9.3.2:2 Following Error Faults

When the position error reaches the programmed fault threshold, the amplifier immediately faults. (The following error fault can be disabled.) For detailed information, see Following Error Fault Details


9.3.3:3 Following Error Warnings

When the position error reaches the programmed warning threshold, the amplifier immediately sets the following error warning bit in the status word. This bit can be read over the CAN network. It can also be used to activate a digital output.

9.3.4:4 Position and Velocity Tracking Windows

When the position error exceeds the programmed tracking window value, a status word bit is set. The bit is not reset until the position error remains within the tracking window for the programmed tracking time. A similar method is used to handle velocity errors. For detailed information, see Tracking Window Details

9.3.5:5 Following Error Fault Details

Position Error Reaches Fault Level

As described earlier, position error is the difference between the limited position output of the trajectory generator and the actual position. When position error reaches the programmed Following Error Fault level, the amplifier faults (unless the following error fault is disabled.) As with a warning, a status bit is set. In addition, the fault is recorded in the error log. See Error Log.

Additional responses and considerations depend on whether the fault is non-latched or latched, as described below.

Amplifier Response to Non-Latched Following Error Fault

When a non-latched following error fault occurs, the amplifier drops into velocity mode and applies the Fast Stop Ramp deceleration rate to bring the motor to a halt. The amplifier PWM output stage remains enabled, and the amplifier holds the velocity at zero, using the velocity loop.

Resuming Operations After a Non-Latched Following Error Fault

The clearing of a non-latched following error depends on the amplifier’s mode of operation. Issuing a new trajectory command over the CAN bus, the ASCII interface, or DeviceNet will clear the fault and return the amplifier to normal operating condition.

If the amplifier is receiving position commands from the digital or differential inputs, then the amplifier must be disabled and then re-enabled using the amplifier’s enable input or though software commands. After re-enabling, the amplifier will operate normally.

Amplifier Response to a Latched Following Error Fault

When a latched following error fault occurs, the amplifier disables the output PWM stage without first attempting to apply a deceleration rate

Resuming Operations After a Latched Following Error Fault

A latched following error fault can be cleared using the steps used to clear other latched faults:
•

  • Power-cycle the amplifier
    •
  • Cycle (disable and then enable) an enable input that is configured as Enables with Clear Faults or Enables with Reset
    •
  • Access the CME 2 Control Panel and press Clear Faults or Reset
    •
  • Clear the fault over the CANopen network or serial bus

9.3.6:6 Tracking Window Details

Proper Tracking Over Time

As described earlier, position error is the difference between the limited position output of the trajectory generator and the actual position. Velocity error is the difference between commanded and actual velocity.

When the position or velocity error exceeds the programmed tracking window value, a status word bit is set. The bit is not reset until the error remains within the tracking window for the programmed tracking time.

Velocity Tracking Illustration

The following diagram illustrates the use of tracking window and time settings in velocity mode. 

image.pngDiagram: velocity tracking window and tracking time

Diagram description (text version): Velocity tracking window in velocity mode: the Limited Velocity (command) ramps up and settles; the Actual Velocity overshoots and oscillates around it. A ± Tracking Window band is drawn around the limited velocity. The Tracking Window Output goes active as soon as the actual velocity leaves the window and goes inactive only after the actual velocity has stayed inside the window for the Tracking Time.

Słowa kluczowe

błędy, latching, kasowanie błędów, following error, uchyb nadążania, ostrzeżenie, tracking window, okno śledzenia, przegrzanie, przepięcie, zwarcie