Appendix D: Low-Pass and Bi-Quad Filters
Streszczenie: Filtry dolnoprzepustowe i Bi-Quad: gdzie są dostępne (filtry pętli prędkości, filtr wejścia analogowego), klasy i typy filtrów (jednobiegunowy, Butterworth 2-biegunowy, Bi-Quad) oraz ustawianie parametrów.
EN: Low-pass and bi-quad filters: where they are used, filter classes/types and setting parameters.
Dotyczy: program CME 2 do konfiguracji i strojenia serwonapędów oraz napędów krokowych Copley Controls (m.in. Xenus, Accelnet, Stepnet, Accelus, Junus)
Źródło: dokumentacja producenta (Copley Controls CME 2 User Guide); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt
CME 2 supports 2 classes of filters on the analog input and on the Velocity Loop command and output: the Low-Pass and the Custom Bi-Quad. The Low-Pass filter class includes the Single-Pole and the Two-Pole Butterworth filter types.
Set Filter Parameters:Parameters
1.
Opening the filter screens
| Velocity
| Analog Input Filter |
|---|---|
| Click V Loop to open the Velocity Loop screen. | Click Analog Command to open the Analog Command screen. |
| Click Command Filter or Output Filter to open the filter screen. | Click Analog Input Filter to open the filter screen. |
The velocity loop and analog input filter controls are identical. The filter window label indicates the source of the filter call and the target of the filter changes. The sample below shows the Velocity Loop Output Filter screen.

2 Adjust the filter settings described below
| Filter Class/Type | Description |
|---|---|
| Low-Pass / Single Pole | The single-pole low pass filter is the simplest filter. The value entered in the Cut-off Frequency field provides the -3 db point. The filter will attenuate at -20 db/decade past the cut-off frequency, reducing excitation of high frequency resonance. |
| Low-Pass / 2 Pole Butterworth | The Butterworth filter is a maximally flat low pass filter. This second order two-pole filter has a damping ratio of 0.707 and produces no peaking in the Bode plot. The value entered in the Cut off Frequency field provides the -3 db point. The filter attenuates at -40 db/decade past the cut-off frequency. The phase-lag at lower frequencies is greater than the phase lag of other second order filters that exhibit more peaking. |
| Custom Bi-Quad | The Bi-Quadratic filter has two quadratic terms: one in the numerator, and one in the denominator. The numerator affects the filter’s two zeros and the denominator affects the filter’s two poles. Many filter classes and types can be expressed in the Bi-Quad form by entering the coefficients. The coefficients can be calculated using any commercially available math software package and entered as floating point numbers. However, due to the fixed-point representation, the numbers may be rounded. |
Słowa kluczowe
filtr dolnoprzepustowy, Butterworth, Bi-Quad, częstotliwość odcięcia, filtr pętli prędkości, filtr wejścia analogowego