Bootstrak Skip to main content

4. Functions (4.13–4.24) – motion and operating mode functions

Streszczenie: Funkcje Indexer 2, część 2: funkcje ruchu i trybów pracy – Velocity Move (tryb pozycyjny i prędkościowy), Move (względny/bezwzględny, profil trapezowy/S-curve), Home, Current Move, Analog Velocity Mode, Analog Position Mode, Disable Amplifier, Camming Internal Master, Camming, Digital Position Mode i Velocity Loop Single Pole Out – z parametrami i jednostkami rejestrów.
EN: Indexer 2 functions part 2: motion and operating mode functions.

Dotyczy: serwonapędy Copley Controls z programem Indexer 2 (CVM), program CME 2
Źródło: dokumentacja producenta (Copley Controls Indexer 2 Program User’s Guide); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt

4.13 Velocity Move Position Mode

4.13.1 Velocity Move Position Mode Function Overview

This function is used to change the operating mode of the amplifier to programmed position mode and configures a constant velocity trajectory.

4.13.2 Adding a Velocity Move Position Mode Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

 Click Motion:Velocity Move Position Mode to select the function. Click Add to add it to the sequence.

The Program tab displays the Velocity Move parameters. 

Screenshot: Program tab – Velocity Move Position Mode › Adding a Velocity Move Position Mode Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Function

Velocity Move – parameters

ParameterDescription
VelocityCommanded velocity. Register units: 0.1 counts/s. (Positive values only)
AccelerationAcceleration rate. Register units: 10 counts/s².
DecelerationDeceleration rate. Register units: 10 counts/s².
Direction of MotionPositive or negative.
Wait for at velocityIf checked, sequence execution will wait at this step until the commanded velocity has reached the new value.
Original image of the table (from the PDF manual)

Original table image: Velocity Move – parameters

4.13.3 Velocity Move Position Mode Notes

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

o Motor phasing is not initialized.

o A register used for a function parameter contains a value that is not valid for the parameter. 

4.14 Move

4.14.1 Move Function Overview

The Move function executes a profile move using the specified parameters.

4.14.2 Adding a Move Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonto open the Indexer Functions screen.

 Click Move to select the function. Click Add to add it to the sequence. 

Screenshot: Program tab – Move › Adding a Move Step to a Sequence

Choose appropriate values for the following parameters. Enter number values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions

Move – parameters

ParameterDescription
MoveType of move: Relative – the axis will move the specified distance from the current position; Absolute – the axis will move to the specified absolute position.
TypeType of profile: Trap – the move will use a trapezoidal profile; S Curve – the move will use an S curve profile.
DistanceDistance of a relative move. Register units: counts.
PositionDestination position of an absolute move. Register units: counts.
VelocityVelocity during the constant velocity portion of the move. Register units: 0.1 counts/s.
AccelAcceleration rate of trapezoidal profile or maximum acceleration/deceleration rate of S curve profile. Register units: 10 counts/s².
Decel (Trap move only)Deceleration rate of trapezoidal profile. Register units: 10 counts/s².
Jerk (S-Curve only)Rate of change of acceleration and deceleration of the S curve profile. Register units: 100 counts/s³.
Wait Move DoneIf checked, sequence execution will wait at this step for the commanded move to finish. If an error occurs during the move, the sequence will exit as programmed.
Original image of the table (from the PDF manual)

Original table image: Move – parameters

4.14.3 Move Function Notes

Wait Move Done

If Wait Move Done is not checked and a second move is commanded, the second move executes immediately with the following results:

If the second move is a relative, trapezoidal move, the axis moves the relative distance from where the axis was when the second move was executed.

If the second move is an absolute, trapezoidal move, the axis moves to the position specified by the second move.

If an S curve profile move is executed while another move is still in progress, an error occurs.

Errors

A sequence error will occur if:

The amplifier is hardware disabled when the Move begins, or becomes hardware disabled during the Move.

The amplifier has a fault when the move begins or a fault occurs during the move.

A software travel limit is reached or a hardware limit switch is activated during the move. 

4.15 Home

4.15.1 Home Function Overview

The Home function executes a home command using the method and parameters specified.

4.15.2 Adding a Home Function Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonto open the Indexer Functions screen.

 Click Home to select the function. Click Add to add it to the sequence.

The Program tab displays the Home function parameters.

Screenshot: Program tab – Home › Adding a Home Function Step to a Sequence

Choose appropriate values for the following parameters. Enter number values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions

Home – parameters

ParameterDescription
Homing MethodSelects which homing method will be used. See Homing Method Descriptions (Appendix B).
Direction of MotionSets the initial direction of motion. Positive or Negative.
Fast VelocityThe velocity used to find a limit or home switch. Also used when moving to an offset position, or a resolver or Servo Tube index position. Register units: 0.1 counts/s.
Slow VelocityThe velocity used to find a switch edge, index pulse, or hard stop. Register units: 0.1 counts/s.
Accel/DecelThe acceleration and deceleration rate used during homing. Register units: 10 counts/s².
OffsetThe axis will execute a move of this distance after the reference is found. The actual position will be reset to 0 at this new position and will now be considered home. Register units: counts.
Current LimitThe current used during the home to hard stop method. Register units: 0.01 A.
Delay TimeThe amount time the current limit is applied during the home to hard stop. Register units: ms.
Wait until referencedIf checked, sequence execution will wait at this step for the home move to finish. If a homing error occurs during homing, the Indexer 2 Program will use the Error Handling action selected from the choices: Abort Sequence, or Jump to the specified sequence.
Original image of the table (from the PDF manual)

Original table image: Home – parameters

4.15.3 Home Function Notes

Do not execute a move function until the homing function is complete.

Errors

A sequence error will occur if:

The amplifier is, or becomes, hardware disable during the Homing function.

The amplifier has a fault at the beginning of the Home function or a fault occurs during the function.

Other sequence errors may occur that are specific to the homing method selected. See Homing Method Descriptions.

4.16 Current Move

4.16.1 Current Move Function Overview

This function is used to change the operating mode of the amplifier to programmed current mode and configure the mode.

4.16.2 Adding a Current Move Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Motion:Current Move to select the function. Click Add to add it to the sequence.

The Program tab displays the Current Move parameters. 

Screenshot: Program tab – Current Move › Adding a Current Move Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions

Current Move – parameters

ParameterDescription
CurrentCommanded current. Register units: 0.01 A.
Current RampRate at which the current will change to its commanded value. Register Units: mA/s.
Wait for at commanded currentIf checked, sequence execution will wait at this step until the commanded current has ramped to the new value.
Original image of the table (from the PDF manual)

Original table image: Current Move – parameters

4.16.3 Current Move Notes

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.17 Velocity Move Velocity Mode

4.17.1 Velocity Move Velocity Mode Function Overview

This function is used to change the operating mode of the amplifier to programmed velocity mode and configures a constant velocity trajectory.

4.17.2 Adding a Velocity Move Velocity Mode Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

 Click Motion:Velocity Move Velocity Mode to select the function. Click Add to add it to the sequence.

The Program tab displays the Velocity Move parameters. 

Screenshot: Program tab – Velocity Move Velocity Mode › Adding a Velocity Move Velocity Mode Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions

Velocity Move – parameters

ParameterDescription
VelocityCommanded velocity. Register units: 0.1 counts/s. (Positive values only)
AccelerationAcceleration rate. Register units: 10 counts/s².
DecelerationDeceleration rate. Register units: 10 counts/s².
Direction of MotionPositive or negative.
Wait for at velocityIf checked, sequence execution will wait at this step until the commanded velocity has reached the new value.
Original image of the table (from the PDF manual)

Original table image: Velocity Move – parameters

4.17.3 Velocity Move Velocity Mode Notes

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.18 Analog Velocity Mode

4.18.1 Analog Velocity Mode Function Overview

This function is used to change the operating mode of the amplifier to analog velocity mode and configure the mode.

4.18.2 Adding an Analog Velocity Mode Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Mode:Analog Velocity Mode to select the function. Click Add to add it to the sequence.

The Program tab displays the Analog Velocity Mode parameters. 

Screenshot: Program tab – Analog Velocity Mode › Adding an Analog Velocity Mode Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions

Analog Velocity Mode – parameters

ParameterDescription
ScalingSets the input-voltage to-velocity command ratio. Register units: Counts / second = 10 V.
Dead BandSets dead band. The amplifier treats anything within the dead band ranges as zero, and subtracts the dead band value from all other values. Register units: mV.
OffsetOffset applied to the input voltage. Register units: mV.
Invert CommandInverts polarity of amplifier output with respect to input signal.
Original image of the table (from the PDF manual)

Original table image: Analog Velocity Mode – parameters

4.18.3 Analog Velocity Mode Notes

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.19 Analog Position Mode

4.19.1 Analog Position Mode Function Overview

This function is used to change the operating mode of the amplifier to Analog Position mode and configure the mode.

4.19.2 Adding an Analog Position Mode Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

 Click Mode: Analog Position Mode to select the function. Click Add to add it to the sequence.

The Program tab displays the Analog Position Mode parameters. 

Screenshot: Program tab – Analog Position Mode › Adding an Analog Position Mode Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions 

Analog Position Mode – parameters

ParameterDescription
ScalingControls the input-to-command ratio. Position change produced by +10 Vdc of input. Register units: Counts = 10 V.
Dead BandSets dead band. The amplifier treats anything within the dead band ranges as zero, and subtracts the dead band value from all other values. Register units: mV.
Invert CommandInverts polarity of amplifier output with respect to input signal.
VelocityMaximum velocity that will be commanded during a move. Register units: 0.1 counts/s.
AccelMaximum acceleration that will be used during a move. Register units: 10 counts/s².
DecelMaximum deceleration that will be used during a move. Register units: 10 counts/s².
Original image of the table (from the PDF manual)

Original table image: Analog Position Mode – parameters

4.19.3 Analog Position Mode Notes

The analog position command operates as a relative motion command. When the amplifier is enabled the voltage on the analog input is read. Then, any change in the command voltage will move the axis a relative distance, proportional as programmed to the change in voltage, from its position when enabled.

To use the analog position command as an absolute position command, the amplifier should be homed every time it is enabled. A simple way to accomplish this is to program the priority sequence to use the same input as the enable input. The priority sequence would be programmed to home the axis. In this way, the axis will be automatically homed every time the amplifier is enabled.

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.20 Disable Amplifier

4.20.1 Disable Amplifier Function Overview

This function is used to software disable the amplifier.

4.20.2 Adding an Disable Amplifier Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Mode: Disable Amplifier to select the function. Click Add to add it to the sequence.

4.20.3 Disable Amplifier Notes

The amplifier will automatically re-enable with the execution of any function, such as Home or Move, which requires axis motion.

Errors

This function does not generate an error. 

4.21 Camming Internal Master

4.21.1 Camming Internal Master Function Overview

This function is used to change the velocity of the Camming Internal Master.

4.21.2 Adding a Camming Internal Master Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Mode: Camming Internal Master to select the function. Click Add to add it to the sequence.

The Program tab displays the Camming Internal Master settings. 

Screenshot: Program tab – Camming Internal Master › Adding a Camming Internal Master Step to a Sequence

Choose appropriate values for the following parameter. Enter the velocity directly or

enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to

Pass Values to Functions

Camming Internal Master – parameters

ParameterDescription
VelocityVelocity of the Camming Internal Master. Register units: 0.1 counts/s.
Original image of the table (from the PDF manual)

Original table image: Camming Internal Master – parameters

4.21.3 Camming Internal Master Function Notes

Errors

A sequence error will occur if this function is executed when a register used for a function parameter contains a value that is not valid for the parameter. 

4.22 Camming

4.22.1 Camming Function Overview

This function is used to change the operating mode of the amplifier to Camming and to configure the Camming mode.

4.22.2 Adding a Camming Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Mode: Camming to select the function. Click Add to add it to the sequence.

The Program tab displays the Camming mode settings. 

Screenshot: Program tab – Camming › Adding a Camming Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers to Pass Values to Functions 

Camming – parameters

ParameterDescription
Master InputExternal: Source of camming master pulse is external. Internal: Source of camming master pulse is internal generator. Velocity of internal master pulse is set using the counts/s field. It can also be reset using the Camming Internal Master function.
Trigger TypeControls how execution of a set of Camming moves is triggered. None (Continuous): The active Cam Table is executed continuously. Use Master (Secondary) Encoder Index: The active Cam Table is executed when the amplifier receives an index pulse from the camming master encoder. Index pulses received during execution are ignored. Use Input, Edge: The active Cam Table begins executing on the rising edge of the designated input pin. Use Input, Level: The active Cam Table repeats continuously as long as the designated input is active.
OffsetForward: A delay (in counts) applied before the active Cam Table is executed when the Master is moving forward. Reverse: A delay (in counts) applied before the active Cam Table is executed when the Master is moving in reverse.
Active Cam TableThe table containing the move profile that the amplifier will execute when the camming trigger is activated.
Original image of the table (from the PDF manual)

Original table image: Camming – parameters

4.22.3 Camming Function Notes

The velocity of internal master pulse can be changed using the Camming Internal Master function.

The amplifier will stay in the camming mode of operation until another Indexer 2 Program function changes it or the amplifier is reset or power cycled.

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.23 Digital Position Mode

4.23.1 Digital Position Mode Function Overview

Change the operating mode of the amplifier to Digital Position mode and configure the mode.

4.23.2 Adding an Digital Position Mode Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

Click Mode:Digital Position Mode to select the function. Click Add to add it to the sequence.

The Program tab displays the Digital Position Mode parameters. 

Screenshot: Program tab – Digital Position Mode › Adding an Digital Position Mode Step to a Sequence

Choose appropriate values for the following parameters. Enter numeric values directly

or enter the number (R0-R31) of an Indexer 2 Program register. See Using Registers

to Pass Values to Functions

Digital Position Mode – parameters

ParameterDescription
Control InputPulse and Direction: One input takes a series of pulses as motion step commands, and another input takes a high or low signal as a direction command. Pulse Up / Pulse Down: One input takes each pulse as a positive step command, and another takes each pulse as a negative step command. Quadrature: A/B quadrature commands from a master encoder (via two inputs) provide velocity and direction commands.
Increment position onRising Edge: Increment position on the rising edge of the input pulse. Falling Edge: Increment position on the falling edge of the input pulse.
Stepping ResolutionInput Pulses: Number of Input Pulses/Counts required to produce given number of output counts. Output Counts: Number of Output Counts per given number of input pulses. Range: 1 to 32,767. Register Units: Pulses/Counts.
Invert CommandWhen checked, inverts commanded direction.
VelocityVelocity during the constant velocity portion of the move. Register units: 0.1 counts/s.
AccelAcceleration rate of trapezoidal profile. Register units: 10 counts/s².
DecelDeceleration rate of trapezoidal profile. Register units: 10 counts/s².
Original image of the table (from the PDF manual)

Original table image: Digital Position Mode – parameters

4.23.3 Digital Position Mode Notes

Errors

A sequence error will occur if this function is executed when:

The amplifier is hardware disabled.

The amplifier is faulted.

Motor phasing is not initialized.

A register used for a function parameter contains a value that is not valid for the parameter. 

4.24 Velocity Loop Single Pole Output Filter

4.24.1 Velocity Loop Single Pole Output Filter Function Overview

This function modifies the Velocity Loop Output Filter.

4.24.2 Adding a Velocity Loop Single Pole Output Filter Step to a Sequence

 Click Add New Step Icon: Add Step tool buttonon the Program tab to open Indexer Functions.

 Click Filters:Velocity Loop Single Pole Output Filter to select the function. Click

Add to add it to the sequence.

The Program tab displays the Filter parameters. 

Screenshot: Program tab – Velocity Loop Single Pole Output Filter › Adding a Velocity Loop Single Pole Output Filter Step to a Sequence

 Enter a Cut Off Frequency value of between 1 and 1500.

4.24.3 Velocity Loop Single Pole Output Filter Notes

Errors

This function does not generate sequence errors. 

Słowa kluczowe

Move, Velocity Move, Home, Current Move, Analog Velocity Mode, Analog Position Mode, Disable Amplifier, Camming, Cam Table, Digital Position Mode, pulse and direction, quadrature, trapezoidal, S-curve