5. Function Parameter List – Part 2 (P5–P9)

Streszczenie: Tabela parametrów funkcyjnych KE300 (część 2 z 3): grupy P5–P9 (wyjścia, start/stop, panel, funkcje rozszerzone, zabezpieczenia) – zakresy nastaw, wartości fabryczne i możliwość zmiany.
EN: KE300 function parameter list (part 2 of 3): groups P5–P9 (outputs, start/stop, keypad, enhanced functions, protections) – setting ranges, factory defaults and modification attributes.

Dotyczy: falownik wektorowy Micno KE300 (zasilanie 1AC/3AC 220 V, 3AC 380 V, 3AC 660 V; moce 0,4–630 kW)
Źródło: dokumentacja producenta (Micno KE300 Series Inverter User Manual); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt

Nawigacja: część 2 z 3 · poprzednia: ← Part 1 (P0–P4) · następna: Part 3 (PA–A0, U0) →

5.1 Basic Function Parameter Table (Continued)

Kolumna „Modify” / Modify column: ○ – parameter can be modified in stop and running status; ◎ – cannot be modified in running status; ● – actual detected value, cannot be modified.

P5 Group: Output Terminal

Function codeNameDetailed instructionFactory defaultModify
P5-00HDO terminal output mode selection0: High speed pulse output
1: Open collector output
0○
P5-01HDO open collector output selection0: No output
1: Inverter is running
2: Fault output (fault stop)
3: FDT1 output
4: Frequency arrival
5: Zero-speed running (no output when stop)
6: Motor overload pre-alarm
7: Inverter overload pre-alarm
8: Setting count value arrival
9: Designated count value arrival
10: Length arrival
11: PLC loop completed
12: Accumulated running time arrival
13: Frequency limiting
14: Torque limiting
15: Ready for running
16: AI1 > AI2
17: Frequency upper limit arrival
18: Frequency lower limit arrival
19: Under voltage status output
20: Communication setting
21: Orientation finished (reserved)
22: Orientation approach (reserved)
23: Zero-speed running 2 (output when stop)
24: Accumulated power-on time arrival
25: FDT2 output
26: Frequency 1 arrival output
27: Frequency 2 arrival output
28: Current 1 arrival output
29: Current 2 arrival output
30: Timing arrival output
31: AI1 input over limit
32: Off load
33: Reverse running
34: Zero-current status
35: Module temperature arrival
36: Output current over limit
37: Lower limit frequency arrival (output when stop)
38: Warning output (keep running)
39: Motor over temperature pre-alarm
40: This running time arrival
41: Reserved
0○
P5-02Relay T1 output selectionSame as P5-01 (DO functions 0 ~ 41)2○
P5-03Relay T2 output selectionSame as P5-01 (DO functions 0 ~ 41)0○
P5-04 ~ P5-05Reserved––●
P5-06HDO function selection0: Running frequency
1: Setting frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
6: Pulse input
7: AI1
8: AI2
9: Reserved
10: Length
11: Count value
12: Communication
13: Motor speed
14: Output current (100.0% corresponds to 1000.0A)
15: Output voltage (100.0% corresponds to 1000.0V)
16: Reserved
0○
P5-07AO1 output function selectionSame as P5-06 (functions 0 ~ 16)0○
P5-08AO2 output function selectionSame as P5-06 (functions 0 ~ 16)0○
P5-09HDO output maximum frequency0.01kHz ~ 100.00kHz50.00kHz○
P5-10AO1 offset coefficient-100.0% ~ +100.0%0.0%○
P5-11AO1 gain-10.00 ~ +10.001.00○
P5-12AO2 offset coefficient-100.0% ~ +100.0%0.0%○
P5-13AO2 gain-10.00 ~ +10.001.00○
P5-17HDO open collector output delay time0.0s ~ 3600.0s0.0s○
P5-18Relay 1 output delay time0.0s ~ 3600.0s0.0s○
P5-19Relay 2 output delay time0.0s ~ 3600.0s0.0s○
P5-20 ~ P5-21Reserved––●
P5-22Output terminal valid status selection0: Positive logic
1: Negative logic
Units place: HDO
Tens place: Relay 1
Hundreds place: Relay 2
000○

P6 Group: Start and Stop Control

Function codeNameDetailed instructionFactory defaultModify
P6-00Start mode0: Direct start
1: Speed tracking and restart
2: Pre-excitation start
0○
P6-01Speed tracking mode0: Begin from stop frequency
1: Begin from zero speed
2: Begin from maximum frequency
0◎
P6-02Speed tracking speed1 ~ 10020○
P6-03Start frequency0.00Hz ~ 10.00Hz0.00Hz○
P6-04Start frequency holding time0.0s ~ 100.0s0.0s◎
P6-05DC braking current before start/pre-excitation current0% ~ 100%0%◎
P6-06DC braking time before start/pre-excitation time0.0s ~ 100.0s0.0s◎
P6-07ACC/DEC mode0: Linear ACC/DEC
1: S-curve ACC/DEC A
2: S-curve ACC/DEC B
0◎
P6-08Time of S curve's start part0.0% ~ (100.0% − P6-09)30.0%◎
P6-09Time of S curve's end part0.0% ~ (100.0% − P6-08)30.0%◎
P6-10Stop mode0: Deceleration to stop
1: Coast to stop
0○
P6-11DC braking start frequency after stop0.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P6-12DC braking delay time after stop0.0s ~ 100.0s0.0s○
P6-13DC braking current after stop0% ~ 100%0%○
P6-14DC braking time after stop0.0s ~ 100.0s0.0s○
P6-15Braking usage ratio0% ~ 100%100%○

P7 Group: Keypad and Display

Function codeNameDetailed instructionFactory defaultModify
P7-00Inverter rated power0.1kW ~ 1000.0kWModel dependent●
P7-01QUICK/JOG function selection0: Invalid
1: Switching between keypad command and remote command (terminal command and communication command)
2: FWD/REV switching
3: Forward jog
4: Reverse jog
0◎
P7-02STOP/RST function selection0: Valid when keypad control
1: Always valid
1○
P7-03Running status display 10000 ~ FFFF
Bit00: Running frequency 1 (Hz)
Bit01: Setting frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI status
Bit08: DO status
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: Radiator temperature
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID setting
81F○
P7-04Running status display 20000 ~ FFFF
Bit00: PID feedback
Bit01: PLC step
Bit02: HDI input pulse frequency (kHz)
Bit03: Running frequency 2 (Hz)
Bit04: Remain running time
Bit05: AI1 voltage before calibration (V)
Bit06: AI2 voltage before calibration (V)
Bit07: Reserved
Bit08: Linear speed
Bit09: Current power-on time (hour)
Bit10: Current running time (min)
Bit11: HDI input pulse frequency (Hz)
Bit12: Communication setting value
Bit13: Reserved
Bit14: Main frequency A display (Hz)
Bit15: Auxiliary frequency B display (Hz)
0○
P7-05Stop status display0000 ~ FFFF
Bit00: Setting frequency (Hz)
Bit01: Bus voltage (V)
Bit02: DI input status
Bit03: DO output status
Bit04: AI1 voltage (V)
Bit05: AI2 voltage (V)
Bit06: Radiator temperature
Bit07: Count value
Bit08: Length value
Bit09: PLC step
Bit10: Load speed
Bit11: PID setting
Bit12: HDI input pulse frequency (kHz)
73○
P7-06Load speed display coefficient0.0001 ~ 6.50003.0000○
P7-07IGBT module temperature0.0 °C ~ 100.0 °C–●
P7-08Inverter rated voltage1V ~ 2000VModel dependent●
P7-09Accumulated running time0h ~ 65535h–●
P7-10Model No.––●
P7-11Software version No.––●
P7-12Load speed display decimal place0: 0 decimal place
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places
1○
P7-13Accumulated power-on time0h ~ 65535h–●
P7-14Accumulated power consumption0kW ~ 65535kW–●

P8 Group: Enhanced Function

Function codeNameDetailed instructionFactory defaultModify
P8-00Jog running frequency0.00Hz ~ P0-10 (max. frequency)2.00Hz○
P8-01Jog acceleration time0.1s ~ 3600.0s20.0s○
P8-02Jog deceleration time0.1s ~ 3600.0s20.0s○
P8-03Acceleration time 20.1s ~ 3600.0sModel dependent○
P8-04Deceleration time 20.1s ~ 3600.0sModel dependent○
P8-05Acceleration time 30.1s ~ 3600.0sModel dependent○
P8-06Deceleration time 30.1s ~ 3600.0sModel dependent○
P8-07Acceleration time 40.1s ~ 3600.0sModel dependent○
P8-08Deceleration time 40.1s ~ 3600.0sModel dependent○
P8-09Jump frequency 10.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P8-10Jump frequency 20.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P8-11Jump frequency amplitude0.00Hz ~ P0-10 (maximum frequency)0.01Hz○
P8-12FWD/REV dead time0.0s ~ 3600.0s0.0s○
P8-13Reverse control0: Enable
1: Disable
0○
P8-14Action when setting frequency lower than frequency lower limit0: Running at frequency lower limit
1: Stop
2: Zero-speed running
0○
P8-15Droop control0.00Hz ~ 10.00Hz0.00Hz○
P8-16Accumulated power-on arrival time0h ~ 36000h0h○
P8-17Accumulated running arrival time0h ~ 36000h0h○
P8-18Power-on running command valid protection selection0: No protection
1: Protection
0○
P8-19Frequency detection value (FDT1)0.00Hz ~ P0-10 (maximum frequency)50.00Hz○
P8-20Frequency detection lagging value (FDT1)0.0% ~ 100.0% (FDT1 level)5.0%○
P8-21Frequency arrival detection amplitude0.0% ~ 100.0% (maximum frequency)0.0%○
P8-22Jump frequency control during ACC/DEC0: Invalid
1: Valid
0○
P8-25Acceleration time 1 and acceleration time 2 switching frequency point0.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P8-26Deceleration time 1 and deceleration time 2 switching frequency point0.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P8-27Terminal jog priority0: Invalid
1: Valid
0○
P8-28Frequency detection value (FDT2)0.00Hz ~ P0-10 (maximum frequency)50.00Hz○
P8-29Frequency detection lagging value (FDT2)0.0% ~ 100.0% (FDT2 level)5.0%○
P8-30Any arrival frequency detection value 10.00Hz ~ P0-10 (maximum frequency)50.00Hz○
P8-31Any arrival frequency detection amplitude 10.0% ~ 100.0% (maximum frequency)0.0%○
P8-32Any arrival frequency detection value 20.00Hz ~ P0-10 (maximum frequency)50.00Hz○
P8-33Any arrival frequency detection amplitude 20.0% ~ 100.0% (maximum frequency)0.0%○
P8-34Zero-current detection level0.0% ~ 300.0%
100.0% corresponds to motor rated current
5.0%○
P8-35Zero-current detection delay time0.01s ~ 360.00s0.10s○
P8-36Output current over limit value0.0% (no detection)
0.1% ~ 300.0% (motor rated current)
200.0%○
P8-37Output current over limit detection delay time0.00s ~ 360.00s0.00s○
P8-38Any arrival current 10.0% ~ 300.0% (motor rated current)100.0%○
P8-39Any arrival current 1 amplitude0.0% ~ 300.0% (motor rated current)0.0%○
P8-40Any arrival current 20.0% ~ 300.0% (motor rated current)100.0%○
P8-41Any arrival current 2 amplitude0.0% ~ 300.0% (motor rated current)0.0%○
P8-42Timing function selection0: Invalid
1: Valid
0○
P8-43Timing running time selection0: P8-44
1: AI1
2: AI2
3: Keypad potentiometer
Analog input scale corresponds to F8-44 (i.e. P8-44)
0○
P8-44Timing running time0.0 min ~ 3600.0 min0.0 min○
P8-45AI1 input voltage protection lower limit0.00V ~ P8-463.10V○
P8-46AI1 input voltage protection upper limitP8-45 ~ 10.00V6.80V○
P8-47Module temperature arrival0 °C ~ 100 °C75 °C○
P8-48Cooling fan control0: Fan runs when inverter running
1: Fan always runs
0○
P8-49Wake up frequency0.0 ~ PA-04 (PID given feedback range)3.0○
P8-50Wake up delay time0.0s ~ 3600.0s0.0s○
P8-51Dormancy frequency0.00Hz ~ P0-10 (maximum frequency)0.00Hz○
P8-52Dormancy delay time0.0s ~ 3600.0s0.0s○
P8-53Running arrival time setting0.0 min ~ 3600.0 min0.0 min○

P9 Group: Fault and Protection

Function codeNameDetailed instructionFactory defaultModify
P9-00Motor overload protection selection0: Disable
1: Enable
1○
P9-01Motor overload protection gain0.20 ~ 10.001.00○
P9-02Motor overload pre-alarm coefficient50% ~ 100%80%○
P9-03Stall over-voltage gain0 ~ 1000○
P9-04Stall over-voltage point / braking threshold120% ~ 150%130%○
P9-05Stall over current gain1 ~ 10020○
P9-06Stall over-current point100% ~ 200%160%○
P9-07Short-circuit to ground protection selection when power-on0: Invalid
1: Valid
1○
P9-08Fast current limitation0: Disable
1: Enable
1○
P9-09Fault auto reset times0 ~ 50○
P9-10Fault HDO acts selection in fault auto reset0: No action
1: Action
0○
P9-11Fault auto reset interval0.1s ~ 100.0s1.0s○
P9-12Input phase failure protection selection0: Disable
1: Enable
0○
P9-13Output phase failure protection selection0: Disable
1: Enable
1○
P9-14The first fault type0: No fault
1: Reserved
2: Acc over current
3: Dec over current
4: Over current in constant speed
5: Over voltage in Acc process
6: Over voltage in Dec process
7: Over voltage in constant speed
8: Reserved
9: Under voltage
10: Inverter overload
11: Motor overload
12: Input side phase failure
13: Output side phase failure
14: Module overheat
15: External fault
16: Communication fault
17: Contactor fault
18: Current detection fault
19: Motor autotuning fault
20: Reserved
21: Parameter R/W fault
22: Inverter hardware fault
23: Motor short circuit to ground fault
24: Reserved
25: Reserved
26: Running time arrival
27: Customized fault 1
28: Customized fault 2
29: Power-on time arrival
30: Off load
31: PID feedback lost when running
40: Fast current limiting over time
41: Reserved
42: Speed deviation oversize
43: Motor over speed
–●
P9-15The second fault typeSame as P9-14–●
P9-16The third (latest) fault typeSame as P9-14–●
P9-17Frequency at the third (latest) fault––●
P9-18Current at the third (latest) fault––●
P9-19Bus voltage at the third (latest) fault––●
P9-20Input terminal's status at the third (latest) fault––●
P9-21Output terminal's status at the third (latest) fault––●
P9-22Inverter status at the third (latest) fault––●
P9-23Power-on time at the third (latest) fault––●
P9-24Running time at the third (latest) fault––●
P9-27Frequency at the second fault––●
P9-28Current at the second fault––●
P9-29Bus voltage at the second fault––●
P9-30Input terminal's status at the second fault––●
P9-31Output terminal's status at the second fault––●
P9-32Inverter status at the second fault––●
P9-33Power-on time at the second fault––●
P9-34Running time at the second fault––●
P9-37Frequency at the first fault––●
P9-38Current at the first fault––●
P9-39Bus voltage at the first fault––●
P9-40Input terminal's status at the first fault––●
P9-41Output terminal's status at the first fault––●
P9-42Inverter status at the first fault––●
P9-43Power-on time at the first fault––●
P9-44Running time at the first fault––●
P9-47Action selection 1 for fault protectionUnits place: motor overload (11)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place: input phase failure (12)
Hundreds place: output phase failure (13)
Thousands place: external fault (15)
Ten thousands place: communication fault (16)
00000○
P9-48Fault protection action selection 2Units place: encoder/PG card fault
0: Coast to stop
Tens place: function code R/W fault
0: Coast to stop
1: Dec-to-stop
Hundreds place: reserved
Thousands place: motor over heat (25)
Ten thousands place: running time arrival (26)
00000○
P9-49Fault protection action selection 3Units place: customized fault 1 (27)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place: customized fault 2 (28)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Hundreds place: power-on time arrival (29)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Thousands place: off load (30)
0: Coast to stop
1: Dec-to-stop
2: Decelerate to 7% of motor rated power, then keep running; run at setting frequency when no off-load
Ten thousands place: PID feedback lost when running (31)
0: Coast to stop
1: Dec-to-stop
2: Keep running
00000○
P9-50Fault protection action selection 4Units place: speed deviation oversize (42)
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place: motor over speed (43)
Hundreds place: initial place fault (51)
00000○
P9-54Running frequency selection when fault0: Run at current running frequency
1: Run at setting frequency
2: Run at upper limit frequency
3: Run at lower limit frequency
4: Run at abnormal backup frequency
0○
P9-55Abnormal backup frequency60.0% ~ 100.0% (100.0% corresponds to maximum frequency P0-10)100.0%○
P9-56 ~ P9-58Reserved––●
P9-59Instantaneous power-off action selection0: Invalid
1: Deceleration
2: Dec-to-stop
0○
P9-60Recover judgment voltage when instantaneous power-off80 ~ 100.0%90.0%○
P9-61Recover judgment time when instantaneous power-off0.00s ~ 100.00s0.50s○
P9-62Action judgment voltage when instantaneous power-off60.0% ~ 100.0% (standard bus voltage)80.0%○
P9-63Off-load protection selection0: Disable
1: Enable
0○
P9-64Off-load detection level0.0 ~ 100.0%10.0%○
P9-65Off-load detection time0.0 ~ 60.0s1.0s○