6. Parameter Description – Part 2 (Groups P1–P3)
Streszczenie: Opis parametrów KE300 (część 2 z 8): parametry silnika i autotuning, sterowanie wektorowe (pętla prędkości, limit momentu) oraz sterowanie V/F (krzywe, boost, kompensacja poślizgu).
EN: KE300 parameter description (part 2 of 8): motor parameters and autotuning, vector control (speed loop, torque limit) and V/F control (curves, boost, slip compensation).
Dotyczy: falownik wektorowy Micno KE300 (zasilanie 1AC/3AC 220 V, 3AC 380 V, 3AC 660 V; moce 0,4–630 kW)
Źródło: dokumentacja producenta (Micno KE300 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt
Nawigacja: część 2 z 8 · ← poprzednia część (Part 1 (Group P0)) · następna część (Part 3 (Group P4)) →
Group P1 Motor Parameters
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P1-00 | Motor type | 0 | 0: Common asynchronous motor 1: Variable frequency asynchronous motor |
| P1-01 | Motor rated power | Model dependent | 0.1kW ~ 1000.0kW |
| P1-02 | Motor rated voltage | Model dependent | 1V ~ 2000V |
| P1-03 | Motor rated current | Model dependent | 0.01A ~ 655.35A (inverter power ≤ 55kW) 0.1A ~ 6553.5A (inverter power > 55kW) |
| P1-04 | Motor rated frequency | Model dependent | 0.01Hz ~ P0-10 (maximum frequency) |
| P1-05 | Motor rated speed | Model dependent | 1rpm ~ 65535rpm |
- Please set the parameters correctly according to the motor nameplate.
- In order to achieve superior control performance, please perform motor parameters autotuning. The accuracy of autotuning is closely related to the correct setting of the rated motor parameters.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P1-06 | Motor stator resistance | Model dependent | 0.001Ω ~ 65.535Ω (inverter power ≤ 55kW) 0.0001Ω ~ 6.5535Ω (inverter power > 55kW) |
| P1-07 | Motor rotor resistance | Model dependent | 0.001Ω ~ 65.535Ω (inverter power ≤ 55kW) 0.0001Ω ~ 6.5535Ω (inverter power > 55kW) |
| P1-08 | Motor leakage inductance | Model dependent | 0.01mH ~ 655.35mH (inverter power ≤ 55kW) 0.001mH ~ 65.535mH (inverter power > 55kW) |
| P1-09 | Motor mutual inductance | Model dependent | 0.1mH ~ 6553.5mH (inverter power ≤ 55kW) 0.01mH ~ 655.35mH (inverter power > 55kW) |
| P1-10 | Motor current without load | Model dependent | 0.01A ~ P1-03 (inverter power ≤ 55kW) 0.1A ~ P1-03 (inverter power > 55kW) |
P1-06 ~ P1-10 are motor parameters, which cannot be found on the motor nameplate, and are obtained via the inverter autotuning. The static autotuning only can obtain P1-06 ~ P1-08. The rotation autotuning not only can obtain P1-06 ~ P1-10, but also can get current loop PI parameter, etc. When P1-01 or P1-02 changed, the inverter will change P1-06 ~ P1-10 automatically, and restore P1-06 ~ P1-10 as standard Y series motor parameters.
If motor parameters autotuning failed in the site, please input the related parameters provided by the motor manufacturer.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P1-11 | Motor parameters autotuning | 0 | 0: No operation 1: Static autotuning 2: Rotation autotuning |
0: No operation, prohibit motor parameter autotuning.
1: Motor parameter static autotuning, suitable for the applications which the asynchronous motor is not easy to disconnect with the load, and cannot make rotation autotuning.
Before static autotuning, please set the motor type and motor parameters (P1-00 ~ P1-05) correctly. The inverter can obtain P1-06 ~ P1-08 via static autotuning.
Action description: Set the function code to be 1, the keypad displays “TUNE”, then press RUN key, the inverter will make static autotuning.
2: Motor parameter rotation autotuning
To ensure the dynamic control performance of inverter, please select rotation autotuning. During the rotation autotuning, the motor must be disconnected with the load (i.e. no-load). During rotation autotuning, the inverter will make static autotuning at first, and then accelerates to 80% motor rated frequency according to acceleration time P0-17, holding for a while, at last decelerates to stop according to deceleration time P0-18 and finish autotuning.
Before rotation autotuning, please set motor type and motor parameters P1-00 ~ P1-05, during rotation autotuning, the inverter can obtain P1-06~P1-10, vector control current loop PI parameters P2-13 ~ P2-16.
Action description: Set the function code to 2, the keypad displays “TUNE”, then press RUN key, the inverter will make rotation autotuning.
Note: Autotuning is valid only on keypad operation mode, cannot make autotuning under terminal and communication operation modes.
Group P2 Vector Control Parameters
Group P2 is valid only for vector control. That is to say, when P0-01=0 or 1, it is valid, and when P0-01=2, it is invalid
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P2-00 | Speed loop proportional gain 1 | 30 | 1 ~ 100 |
| P2-01 | Speed loop integration time 1 | 0.50s | 0.01s ~ 10.00s |
| P2-02 | Low switching frequency | 5.00Hz | 0.00 ~ P2-05 |
| P2-03 | Speed loop proportional gain 2 | 20 | 1 ~ 100 |
| P2-04 | Speed loop integration time 2 | 1.00s | 0.01s ~ 10.00s |
| P2-05 | High switching frequency | 10.00Hz | P2-02 ~ P0-10 (maximum frequency) |
P2-00 and P2-01 are PI adjustment parameters when the running frequency is lower than low switching frequency (P2-02). P2-03 and P2-04 are PI adjustment parameters when the running frequency is higher than high switching frequency (P2-05). PI parameter of frequency channel between low switching frequency and high switching frequency is linear switching between two groups of PI parameters, as shown in the figure below:
Diagram description (text version): Figure 6-2 PI parameter diagram: below the low switching frequency P2-02 the speed loop uses PI parameters P2-00/P2-01; above the high switching frequency P2-05 it uses P2-03/P2-04; between P2-02 and P2-05 the PI parameters change linearly from the first to the second set.
The speed dynamic response characteristics of the vector control can be adjusted by setting the proportional coefficient and integration time of the speed regulator.
Increasing the proportional gain or reducing the integration time can accelerate the dynamic response of the speed loop. However, if the proportional gain is too large or the integration time is too short, it will cause the oscillation of the system.
Recommended adjustment method:
If factory default cannot meet the requirements, the relevant parameter values can be subject to fine tuning.
Increase the proportional gain while ensuring no oscillation to the system, and then reduce the integration time to ensure that the system has quick response characteristics and small overshoot.
Caution: Improper PI parameter setting may cause too large speed overshoot. Voltage fault may occur when the overshoot drops.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P2-06 | Vector control slip compensation coefficient | 100% | 50% ~ 200% |
For sensorless vector control, this parameter is used to adjust the speed stabilizing precision of the motor.
When the speed is too low due to heavy load of motor, this parameter needs to be enlarged, vice versa.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P2-07 | Speed loop filter time | 0.000s | 0.000s ~ 0.100s |
Under vector control mode, the output of speed loop regulator is torque current command. This parameter is used to filter the torque command. This parameter needs no adjustment generally and this filter time can be increased in case of huge speed fluctuation. In case of oscillation of motor, this parameter should be reduced properly.
The speed loop filter time is low, and the inverter output torque may fluctuate greatly, but the response is quick.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P2-08 | Vector control over excitation gain | 64 | 0 ~ 200 |
During deceleration, over excitation control can suppress bus voltage increase, avoid over voltage fault.
The bigger over excitation gain is, the better the suppression result is.
For the application which over voltage fault happens frequently during deceleration, the over excitation gain needs to be increased. But the current would be increased if the over excitation is too bigger, so you need to set the suitable over excitation gain.
For the small inertia situation, voltage doesn’t increase during motor deceleration, please set over excitation gain to 0. For the application with braking resistor, please also set over excitation gain to 0.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P2-09 | Torque upper limit source under speed control mode | 0 | 0: P2-10 1: AI1 2: AI2 3: Keypad potentiometer 4: High speed pulse HDI 5: Communication |
| P2-10 | Torque upper limit digital setting | 150.0% | 0.0% ~ 200.0% |
In the speed control mode, the maximum of the inverter output torque is controlled by the torque upper limit source.
P2-09 is used to select the setting source of torque upper limit. When setting via the analog value, high speed pulse HDI, communication, 100% of the relevant setting corresponds to P2-10, and 100% of P2-10 is the inverter rated torque.
Group P3 V/F Control Parameters
This group of function code is enabled only for V/F control (P0-01=2) and is invalid for vector control. V/F control is applicable for the general loads such as fan and pump or the applications where one inverter drives multiple motors or the inverter power is one level lower or higher than the motor power.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-00 | V/F curve setting | 0 | 0: Linear V/F curve 1: Multiple-point V/F curve 2: Square V/F curve 3: 1.2 power V/F 4: 1.4 power V/F 6: 1.6 power V/F 8: 1.8 power V/F |
0: Linear V/F curve. It is suitable for common constant torque load.
1: Multiple-point V/F curve. It is suitable for the special loads such as dehydrator and centrifugal machine.
2: Square V/F curve. It is suitable for the centrifugal loads such as fan and pump.
3~8: VF curve between linear VF and square VF.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-01 | Torque boost | Model dependent | 0.0% ~ 30% |
| P3-02 | Cut-off frequency of torque boost | 50.00Hz | 0.00Hz ~ P0-10 (maximum frequency) |
To compensate the low frequency torque characteristics of V/F control, it can boost the inverter output voltage during low frequency. If the torque boost is set to too large, the motor may be over heat, and the inverter may be over current.
Adjust this parameter according to the different loads. Increase this parameter for heavy load, reduce it for light load.
When the torque boost is set to 0.0, the inverter will adopt auto torque boost.
Cut-off frequency of torque boost: Under this frequency, the torque boost is valid. If it exceeds this setting frequency, the torque boost is invalid. Refer to Figure 6-3 for details.
Diagram description (text version): Figure 6-3 Manual torque boost: output voltage versus output frequency. With manual torque boost the V/F line starts at the boost voltage V1 at 0 Hz instead of 0 V and rises linearly; above the cut-off frequency f1 the curve joins the normal V/F line, reaching the maximum output voltage Vb at the rated running frequency fb (dashed line: V/F curve without boost).
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-03 | V/F frequency point 1 | 0.00Hz | 0.00Hz ~ P3-05 |
| P3-04 | V/F voltage point 1 | 0.0% | 0.0% ~ 100.0% |
| P3-05 | V/F frequency point 2 | 0.00Hz | P3-03 ~ P3-07 |
| P3-06 | V/F voltage point 2 | 0.0% | 0.0% ~ 100.0% |
| P3-07 | V/F frequency point 3 | 0.00Hz | P3-05 ~ P1-04 (motor rated frequency; the source says “motor rated power”) |
| P3-08 | V/F voltage point 3 | 0.0% | 0.0% ~ 100.0% |
Multi-step V/F curve is defined by P3-03 to P3-08.
The curve of multi point V/F is generally set according to the load characteristics of the motor.
- Caution: V1<V2<V3 and F1<F2<F3. The voltage corresponding to low frequency should not be set too high, otherwise it may cause motor overheat or inverter fault.
Diagram description (text version): Multi-point V/F curve: voltage versus frequency through three user points (f1, V1), (f2, V2), (f3, V3) set by P3-03…P3-08, then rising to 100% voltage at the rated frequency fb and staying constant above it. Frequencies and voltages must increase from point 1 to point 3.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-09 | V/F slip compensation gain | 0.0% | 0% ~ 200.0% |
It is valid only for V/F control.
Setting this parameter can compensate the slip of motor speed caused by the load increases, and makes the motor speed stably when the load changes.
V/F slip compensation gain set to 100% means the slip compensation of the motor with rated load is the motor rated slip, which can be calculated according to motor rated power and motor rated speed automatically.
Slip gain adjustment can refer to the following principle: When the load is rated load, the motor speed is basically the same as the target speed. When the values are different, please adjust this gain properly.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-10 | V/F over-excitation gain | 64 | 0 ~ 200 |
During deceleration, over excitation control can suppress bus voltage increase, avoid over voltage fault. The bigger over excitation gain is, the better suppression result is.
For the application which over voltage fault happens frequently during deceleration, the over excitation gain needs to be increased. But the current would be increased if the over excitation is too bigger, so you need to set the suitable over excitation gain.
For the small inertia situation, voltage doesn’t increase during motor deceleration, please set over excitation gain to 0. For the application with braking resistor, please also set over excitation gain to 0.
| Parameter | Name | Factory default | Setting range |
|---|---|---|---|
| P3-11 | V/F oscillation suppression gain | Model dependent | 0 ~ 100 |
Set the gain as small as possible on the premise that there is effective oscillation suppression measure, which can avoid the affect causing to VF running. Set the gain to 0 when the motor has no oscillation. Only when the motor has obvious oscillation, this gain can be increased properly. The bigger the gain is, the better oscillation suppression result will be.
When using this function, please make sure the motor rated current and no load current parameters are accurate, otherwise V/F oscillation suppression result would be bad.