Bootstrak Skip to main content

6. Parameter Description – Part 5 (Groups P7–P8)

Streszczenie: Opis parametrów KE300 (część 5 z 8): panel i wyświetlanie (QUICK/JOG, parametry statusu) oraz funkcje rozszerzone (JOG, czasy ACC/DEC 2–4, częstotliwości skoku, FDT, detekcja prądu, timer, uśpienie i wybudzenie).
EN: KE300 parameter description (part 5 of 8): keypad and display (QUICK/JOG, status display) and enhanced functions (jog, ACC/DEC times 2–4, jump frequencies, FDT, current detection, timer, sleep and wake-up).

Dotyczy: falownik wektorowy Micno KE300 (zasilanie 1AC/3AC 220 V, 3AC 380 V, 3AC 660 V; moce 0,4–630 kW)
Źródło: dokumentacja producenta (Micno KE300 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt

Group P7 Keypad and Display

ParameterNameFactory defaultSetting range
P7-00Inverter rated powerModel dependent0.1kW ~ 1000.0kW

Display inverter rated power.

ParameterNameFactory defaultSetting range
P7-01QUICK/JOG function selection00: Invalid
1: Switching between keypad command and remote command (terminal command and communication command)
2: FWD/REV switching
3: Forward Jog
4: Reverse Jog

QUICK/JOG is a multifunctional key, whose function can be defined by the value

0: This key is invalid

1: Switching between keyboard command and remote operation. It refers to switching of command source, switching between the current command source and the keyboard control (local operation). If the current command source is keyboard control, this key is invalid.

2: Press QUICK/JOG, the running direction of inverter will change. It is only valid when keypad command is valid.

3: It can realize forward jog via QUICK/JOG key.

4: It can realize reverse jog via QUICK/JOG key.

ParameterNameFactory defaultSetting range
P7-02STOP/RST function selection10: Valid when keypad control
1: Always valid
ParameterNameFactory defaultSetting range
P7-03Running status display 11F0000 ~ FFFF

P7-03 – bit assignment

BitDisplayed value
0Running frequency (Hz)
1Setting frequency (Hz)
2DC bus voltage (V)
3Output voltage (V)
4Output current (A)
5Output power (kW)
6Output torque
7DI input status
8DO output status
9AI1 voltage (V)
10AI2 voltage (V)
11Radiator temperature
12Count value
13Length value
14Load speed display
15PID setting

If the above parameters need to be displayed when running, set the corresponding positions to 1, change the binary number into a hexadecimal number and enter it into P7-03.

ParameterNameFactory defaultSetting range
P7-04Running status display 200000 ~ FFFF

P7-04 – bit assignment

BitDisplayed value
0PID feedback
1PLC phase
2HDI frequency (kHz)
3Running frequency 2 (Hz)
4Remain running time
5AI1 voltage before calibration (V)
6AI2 voltage before calibration (V)
7Reserved
8Linear speed
9Current power-on time (Hour)
10Current running time (Min)
11HDO frequency (kHz)
12Communication setting value
13Reserved
14Main frequency A display (Hz)
15Auxiliary frequency B display (Hz)

If the above parameters need to be displayed when running, set the corresponding positions to 1, change the binary number into a hexadecimal number and enter it into P7-04.

Operation display parameter is used to set the parameters which can be viewed when running.

There are at most 32 parameters can be viewed, set the status parameters via the binary bits of P7-03 and P7-04, and the display sequence starts from the lowest order of P7-03.

ParameterNameFactory defaultSetting range
P7-05Stop status display00000 ~ FFFF

P7-05 – bit assignment

BitDisplayed value
0Setting frequency (Hz)
1Bus voltage (V)
2DI input status
3DO output status
4AI1 voltage (V)
5AI2 voltage (V)
6Radiator temperature
7Count value
8Length value
9PLC phase
10Load speed
11PID setting
12HDI frequency
13Reserved
14Reserved
15Reserved

If the above parameters need to be displayed when stopped, set the corresponding positions to 1, change the binary number into a hexadecimal number and enter it into P7-05.

ParameterNameFactory defaultSetting range
P7-06Load speed display coefficient3.00000.0001 ~ 6.5000

The correspondence of the inverter output frequency and the load speed can be adjusted via this parameter when the load speed needs to be displayed.

ParameterNameFactory defaultSetting range
P7-07IGBT module temperature–0.0 °C ~ 100.0 °C

Display IGBT module temperature.

The over temperature protection values of different IGBT modules are not the same.

ParameterNameFactory defaultSetting range
P7-08Inverter rated voltageModel dependent1V ~ 2000V

Display inverter rated voltage

ParameterNameFactory defaultSetting range
P7-09Accumulated running time–0h ~ 65535h

Display the accumulated running time of the inverter. When the running time reaches the value set by P8-17, the digital output terminal outputs ON signal.

ParameterNameFactory defaultSetting range
P7-10Model No.–Inverter model No.
P7-11Software version No.–Control software version No.
P7-12Load speed display decimal place00: 0 decimal places
1: 1 decimal place
2: 2 decimal places
3: 3 decimal places

The parameters are used to set load speed display decimal place. The following load speed calculation format for example:

If load speed display factor (P7-06) is 2.000, load speed decimal place (P7-12) is 2 (2 decimal places), when the running frequency is 40.00Hz, load speed is: 40.00×2.000=80.00 (2 decimal places displayed)

If the inverter stops, load speed is displayed as setting frequency corresponding speed, namely “setting load speed”. If setting frequency=50.00Hz, the stop status load speed is: 50.00×2.000=100.00 (2 decimal places displayed)

ParameterNameFactory defaultSetting range
P7-13Accumulated power-on time0h0h ~ 65535h

Display the accumulated power-on time after production.

When this time reaches the value set by P8-17, the inverter multifunctional digital output function (24) outputs ON signal.

ParameterNameFactory defaultSetting range
P7-14Accumulated power consumption–0kW ~ 65535kW

Display the accumulated power consumption till now.

Group P8 Enhanced Function

ParameterNameFactory defaultSetting range
P8-00Jog running frequency2.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-01Jog acceleration time20.0s0.1s ~ 3600.0s
P8-02Jog deceleration time20.0s0.1s ~ 3600.0s

It is used to define the reference frequency and ACC/DEC time of the inverter when jogging. During Jog running, the start mode is fixed to direct start (P6-00=0), the stop mode is fixed to deceleration to stop (P6-10=0).

ParameterNameFactory defaultSetting range
P8-03Acceleration time 2Model dependent0.1s ~ 3600.0s
P8-04Deceleration time 2Model dependent0.1s ~ 3600.0s
P8-05Acceleration time 3Model dependent0.1s ~ 3600.0s
P8-06Deceleration time 3Model dependent0.1s ~ 3600.0s
P8-07Acceleration time 4Model dependent0.1s ~ 3600.0s
P8-08Deceleration time 4Model dependent0.1s ~ 3600.0s

KE300 series inverter supplies 4 kinds of ACC/DEC time. The principles of them are the same. Please refer to description of P0-17 and P0-18 for more details.

User can select the one of 4 kinds ACC/DEC time thought the different combination of DI terminals. See the description of P4-00~P4-05, then pay attention to Function (16) & Function (17) and Attached table 2.

ParameterNameFactory defaultSetting range
P8-09Jump frequency 10.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-10Jump frequency 20.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-11Jump frequency amplitude0.00Hz0.00 ~ P0-10 (maximum frequency)

By means of setting jump frequency, the inverter can keep away from the mechanical resonance with the load. P8.09 and P8.10 are center value of frequency to be skipped.

If both P8-09 and P8-10 are 0, the jump frequency function is invalid no matter what P8.11 is.

Diagram: Figure 6-13 Jump frequency diagram

Diagram description (text version): Figure 6-13 Jump frequency: while the output frequency ramps up over time, it skips the bands around jump frequency 1 and jump frequency 2; each band extends by the jump frequency amplitude above and below the jump frequency, so the inverter does not run steadily inside these bands.

ParameterNameFactory defaultSetting range
P8-12FWD/REV dead time0.0s0.00s ~ 3600.0s

FWD/REV dead time: The waiting and holding time before the motor changes its spinning direction after the inverter's output frequency is decreased to zero. It is the time taken by the motor to change its spinning direction when the inverter receives REV command during its running process. The time is shown in Figure 6-14:

Diagram: Figure 6-14 FWD/REV dead time diagram

Diagram description (text version): Figure 6-14 FWD/REV dead time: the output frequency decelerates from forward running to 0 Hz, stays at 0 Hz for the dead time (P8-12) and then accelerates in the reverse direction.

FWD/REV dead time: The waiting and holding time before the motor changes its spinning direction after the inverter's output frequency is decreased to zero. It is the time taken by the motor to change its spinning direction when the inverter receives REV command during its running process. The time is shown in Figure 6-14:

ParameterNameFactory defaultSetting range
P8-13Reverse control00: Valid
1: Invalid

It is used to set if the inverter can run reverse, P8-13 is set to 1 for the applications that the motor can not run reverse.

ParameterNameFactory defaultSetting range
P8-14Action when setting frequency lower than frequency lower limit00: Running at frequency lower limit
1: Stop
2: Zero speed running

It is used to select the inverter running status when the setting frequency is lower than the frequency lower limit.

ParameterNameFactory defaultSetting range
P8-15Droop control0.00Hz0.00Hz ~ 10.00Hz

When several motors drive the same load, each motor's load is different because of the difference of motor's rated speed. The load of different motors can be balanced through droop control function which makes the speed droop along with load increase.

When the motor outputs rated torque, actual frequency drop is equal to P8-15. User can adjust this parameter from small to big gradually during commissioning.

ParameterNameFactory defaultSetting range
P8-16Accumulated power-on arrival time0h0h ~ 36000h

When the accumulated power on time (P7-13) reaches the value set by P8-16, the multifunctional digital DO outputs ON signal.

ParameterNameFactory defaultSetting range
P8-17Accumulated running arrival time0h0h ~ 36000h

It is used to set the running time of the inverter.

When the accumulated running time (P7-09) reaches the value set by P8-17, the multifunctional digital DO outputs ON signal.

ParameterNameFactory defaultSetting range
P8-18Power-on running command valid protection selection00: No protection
1: Protection
  1. If power-on running command is valid (for example, the terminal running command is close before power on), the inverter will not response the running command. After the running command is removed & valid again, the inverter will response.
  2. If the fault reset running command is valid, the inverter will not response the running commend, user must cancel the running command to remove the running protection status.
  3. This code is set to 1 so as to avoid dangerous caused by that motor responses running command during power-on or fault reset.
ParameterNameFactory defaultSetting range
P8-19Frequency detection value (FDT1)50.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-20Frequency detection lag (FDT1)5.0%0.0% ~ 100.0% (FDT1 level)

When the output frequency reaches a certain preset frequency (FDT level), DO terminal will output an ON signal until output frequency drops below a certain frequency of FDT level (FDT level - FDT lag), as shown in following figure.

Diagram: Figure 6-15 FDT level and lag diagram

Diagram description (text version): Figure 6-15 FDT level and lag: the FDT reached signal turns ON when the output frequency rises above the FDT level and turns OFF only when the frequency falls below the FDT level minus the FDT lag (hysteresis).

ParameterNameFactory defaultSetting range
P8-21Frequency arrival detection amplitude0.0%0.00 ~ 100% (maximum frequency)

When output frequency is within the detecting range of reference frequency, an ON-OFF signal will be output. The function can adjust the detecting range.

Diagram: Figure 6-16 Frequency arrival detection diagram

Diagram description (text version): Figure 6-16 Frequency arrival detection: the frequency arrival detection signal is ON while the output frequency is within the detection amplitude band (± P8-21) around the reference frequency – i.e. briefly while accelerating through the band, while running at the reference frequency, and while decelerating through the band.

ParameterNameFactory defaultSetting range
P8-22Jump frequency during ACC/DEC00: Invalid
1: Valid

It is used to set if jump frequency is valid during ACC/DEC.

When valid, the running frequency is in the range of jump frequency, the actual running frequency will skip the boundary of the setting jump frequency.

Diagram: Figure 6-17 Jump frequency during ACC/DEC diagram

Diagram description (text version): Figure 6-17 Jump frequency during ACC/DEC: when P8-22 is valid, the output frequency ramps up and passes through the bands around jump frequency 1 and 2 (± jump frequency amplitude) by jumping vertically across them instead of ramping through.

ParameterNameFactory defaultSetting range
P8-25Acceleration time 1 and acceleration time 2 switching frequency point0.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-26Deceleration time 1 and deceleration time 2 switching frequency point0.00Hz0.00Hz ~ P0-10 (maximum frequency)

This function is valid when don’t use DI terminal to switch ACC/DEC. Suitable for the inverter running process, choose different ACC/DEC time according to the running frequency range (instead of through DI terminals).

Diagram: Figure 6-18 ACC/DEC time switching diagram

Diagram description (text version): Figure 6-18 ACC/DEC time switching: below the switching point P8-25 the inverter accelerates with acceleration time 2, above it with acceleration time 1 up to the setting frequency; when decelerating it uses deceleration time 1 down to P8-26 and deceleration time 2 below P8-26.

During ACC, if the running frequency is lower than P8-25, then select ACC time 2, if the running frequency is higher than P8-25, then select ACC time 1.

During DEC, if the running frequency is higher than P8-26, then select DEC time 1, if the running frequency is lower than P8-26, then select DEC time 2.

ParameterNameFactory defaultSetting range
P8-27Terminal jog priority00: Invalid
1: Valid

It is used to set whether the priority of terminal jog function is the highest.

When terminal jog priority is valid, if terminal jog command appears when running, the inverter switches to terminal jog running status.

ParameterNameFactory defaultSetting range
P8-28Frequency detection value (FDT2)50.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-29Frequency detection lag value (FDT2)5.0%0.0% ~ 100.0% (FDT2 level)

This frequency detection function is the same as FDT1’s, please refer to description of FDT1 (P8-19, P8-20).

ParameterNameFactory defaultSetting range
P8-30Any arrival frequency detection value 150.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-31Any arrival frequency detection amplitude 10.0%0.0% ~ 100.0% (maximum frequency)
P8-32Any arrival frequency detection value 250.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-33Any arrival frequency detection amplitude 20.0%0.0% ~ 100.0% (maximum frequency)

When the output frequency reaches positive or negative detection amplitude of frequency detection value, DO outputs ON signal. KE300 series inverter provides two parameters of any arrival frequency detection value, used to set frequency value and frequency detection range.

Diagram: Figure 6-19 Any arrival frequency detection diagram

Diagram description (text version): Figure 6-19 Any arrival frequency detection: the DO or relay output is ON while the output frequency is within the band of the selected arrival frequency ± frequency detection amplitude – once while accelerating through the band and once while decelerating through it.

ParameterNameFactory defaultSetting range
P8-34Zero-current detection level5.0%0.0% ~ 300.0% (100.0% corresponds to motor rated current)
P8-35Zero-current detection delay time0.10s0.00s ~ 360.00s

When the output current ≤ zero current detection level, lasts for longer than zero current detection delay time, DO terminal outputs ON signal.

Diagram: Figure 6-20 Zero-current detection diagram

Diagram description (text version): Figure 6-20 Zero-current detection: when the output current drops below the zero current detection level P8-34 and stays below it for the delay time P8-35, the zero current detection signal turns ON; it turns OFF when the current rises above the level again.

ParameterNameFactory defaultSetting range
P8-36Output current over limit value200.0%0.0% (no detection)
0.1% ~ 300.0% (motor rated current)
P8-37Output current over limit detection delay time0.00s0.00s ~ 360.00s

When the output current is bigger than or over-limit detection point, lasts for longer than software over current point detection delay time, DO terminal outputs ON signal.

Diagram: Figure 6-21 Output current over limit function diagram

Diagram description (text version): Figure 6-21 Output current over limit: when the output current exceeds the over limit value P8-36 for longer than the detection delay time P8-37, the output current over limit detection signal turns ON.

ParameterNameFactory defaultSetting range
P8-38Any arrival current 1100.0%0.0% ~ 300.0% (motor rated current)
P8-39Any arrival current 1 amplitude0.0%0.0% ~ 300.0% (motor rated current)
ParameterNameFactory defaultSetting range
P8-40Any arrival current 2100.0%0.0% ~ 300.0% (motor rated current)
P8-41Any arrival current 2 amplitude0.0%0.0% ~ 300.0% (motor rated current)

When the output current is in the range of positive or negative detection amplitude of setting any arrival current, DO terminal outputs ON signal. KE300 series inverter provides two parameters of any arrival current and detection amplitude.

Diagram: Figure 6-22 Any arrival current detection diagram

Diagram description (text version): Figure 6-22 Any arrival current detection: the DO or relay output is ON whenever the output current is within the band of the any arrival current ± amplitude, and OFF when the current is outside this band.

ParameterNameFactory defaultSetting range
P8-42Timing function selection00: Invalid
1: Valid
P8-43Timing running time selection00: P8-44
1: AI1
2: AI2
3: Keypad potentiometer
Analog input scale 100% corresponds to P8-44 (the source says F8-44)
P8-44Timing running time0.0Min0.0Min ~ 3600.0Min

The parameters are used to set the inverter timing running function.

When P8-42 timing function selection is valid, timing starts after the inverter starts, reaches the setting timing running time, the inverter stops automatically, meantime, DO terminal outputs ON signal.

Timing starts from 0 when the inverter starts, timing remain running time can be viewed via U0-20.

The timing running time is set by P8-43, P8-44, time unit is minute.

ParameterNameFactory defaultSetting range
P8-45AI1 input voltage protection lower limit3.10V0.00V ~ P8-46
P8-46AI1 input voltage protection upper limit6.80VP8-45 ~ 10.00V

When the analog input AI1 value is bigger than P8-46, or smaller than P8-45, DO terminal outputs “AI1 input over limit” ON signal, used to indicate whether AI1 input voltage is in the setting range.

ParameterNameFactory defaultSetting range
P8-47Module temperature arrival75 °C0 °C ~ 100 °C

When the converter radiator temperature reaches this value, DO outputs “module temperature arrival” ON signal.

ParameterNameFactory defaultSetting range
P8-48Cooling fan control00: Fan runs when operating
1: Fan always runs

It is used to select cooling fan action mode,

When the selection is 0, cooling fans run when the inverter running, when the inverter stops & the radiator temperature is higher than 40℃, cooling fans run.

When the inverter stops & the radiator temperature is lower than 40℃, cooling fans stop.

When the selection is 1, cooling fans always run after power-on.

ParameterNameFactory defaultSetting range
P8-49Wake up frequency3.00.00 ~ PA-04 (PID given feedback range)
P8-50Wake-up delay time0.0s0.0s ~ 3600.0s
P8-51Dormancy frequency0.00Hz0.00Hz ~ P0-10 (maximum frequency)
P8-52Dormancy delay time0.0s0.0s ~ 3600.0s

The parameters are used to achieve dormancy and wake up function in water-supply applications.

During running, when the setting frequency ≤ P8-51 dormancy frequency, lasts for P8-52 delay time, the inverter enters into dormancy status & stops automatically.

When the inverter is in the dormancy status & the present running command is valid, if the setting frequency ≥ P8-49 wake up frequency lasts for P8-50 delay time, the inverter starts.

Normally please set wake up frequency ≥ dormancy frequency. Setting both wake up frequency and dormancy frequency are 0.00Hz, then wake up and dormancy functions are invalid.

When starting dormancy function, if frequency source is set by PID, PA-28 will affect whether dormancy status PID calculates or not, PID stop calculation function must be set to be 1 (namely PA-28=1).

ParameterNameFactory defaultSetting range
P8-53Running arrival time setting0.0Min0.0Min ~ 3600.0Min

When the running time reaches the time set by P8-53, DO outputs “Running arrival time setting” ON signal.

Słowa kluczowe

Micno KE300, opis parametrów, parameter description, P7, P8, QUICK/JOG, wyświetlanie, display, JOG, FDT, częstotliwość skoku, jump frequency, uśpienie, dormancy, wake up