6. Parameter Description – Part 6 (Groups P9–PA)

Streszczenie: Opis parametrów KE300 (część 6 z 8): zabezpieczenia i obsługa błędów (przeciążenie, utyk, auto-reset, rejestr błędów, zanik zasilania, niedociążenie) oraz regulator PID.
EN: KE300 parameter description (part 6 of 8): protections and fault handling (overload, stall, auto reset, fault records, power loss, off-load) and the PID controller.

Dotyczy: falownik wektorowy Micno KE300 (zasilanie 1AC/3AC 220 V, 3AC 380 V, 3AC 660 V; moce 0,4–630 kW)
Źródło: dokumentacja producenta (Micno KE300 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt

Nawigacja: część 6 z 8 · ← poprzednia część (Part 5 (Groups P7–P8)) · następna część (Part 7 (Groups PB–A0)) →

Group P9 Fault and Protection

ParameterNameFactory defaultSetting range
P9-00Motor overload protection selection10: Invalid
1: Valid
P9-01Motor overload protection gain1.000.20 ~ 10.00

P9-00=0: Has no motor overload protection function, may cause the motor overheating damaged.

P9-00=1: The inverter judges whether the motor is overload or not according to the inverse time limit curve of motor overload protection.

The inverse time limit curve of motor overload protection: 220%×(P9-01)×motor rated current, lasts for one minute, the overload fault would be reported; 150%×(P9-01)×motor rated current, lasts for 60 minutes, the overload fault would be reported.

Please set P9-01 according to the motor overload ability. If the parameter is too big, the motor will over heat damage without alarming.

ParameterNameFactory defaultSetting range
P9-02Motor overload pre-warning coefficient80%50% ~ 100%

For safe consideration, there is a pre-warming signal sent to the control system via DO before the motor overload fault protection, the pre-warming coefficient is used to confirm the extent of pre-warming before the motor overload protection. The bigger the parameter is, the smaller the pre-warming lead is.

After the accumulated output current is bigger than (P9-02)*overload inverse time limit curve, DO outputs “motor overload pre-warming” ON signal.

ParameterNameFactory defaultSetting range
P9-03Over-voltage stall gain00 (no over-voltage stall) ~ 100
P9-04Over-voltage stall protection voltage130%120% ~ 150% (three phase)

During deceleration, after DC bus voltage exceeds over-voltage stall protection voltage, the inverter stops deceleration & runs with the current frequency, continue decelerating after bus voltage drops.

Over-voltage stall gain is used to adjust the suppression over-voltage capacity during deceleration. The bigger this value is, the stronger the capacity is. Under the precondition of no over-voltage, please set the gain as small as possible.

For the load with small inertia, the value should be small. Otherwise, the dynamic response of the system will be slow. For the load with big inertia, the value should be big. Otherwise, the suppression result will be poor, and over voltage fault may occur.

When the value is 0, the over voltage stall function is invalid.

ParameterNameFactory defaultSetting range
P9-05Over-current stall gain200 ~ 100
P9-06Over-current stall protection current160%100% ~ 200%

During the inverter ACC/DEC, when the output current exceeds over-current stall protection current, the inverter stops ACC/DEC, runs with the current frequency, continue ACC/DEC after the output current is reduced.

Over-current stall gain is used to adjust the suppression over-current capacity during ACC/DEC. The bigger this value is, the stronger the capacity is. Under the precondition of no over-current, please set the gain as small as possible.

For the load with small inertia, the value should be small. Otherwise, the dynamic response of the system will be slow. For the load with big inertia, the value should be big. Otherwise, the suppression result will be poor, and over-current fault may occur.

When the value is 0, the over-voltage stall function is invalid.

ParameterNameFactory defaultSetting range
P9-07Short circuit to ground protection selection when power-on10: Invalid
1: Valid

It is used to check if the motor is short circuit to ground when the inverter is power on.

If the function is valid, the inverter UVW terminals have output voltage after power on for a while.

ParameterNameFactory defaultSetting range
P9-08Fast current limitation10: Disable
1: Enable
P9-09Fault auto reset times00 ~ 5

After the inverter fails in running process, the inverter stops its output; then performs auto fault reset and continues running after the reset interval defined in P9-11.

P9-09 is used to set fault auto reset times. After this value is exceeded, the inverter will keep fault status.

When the fault auto reset time is setup to 0, there is no auto-reset function, and only manual reset can be done.

ParameterNameFactory defaultSetting range
P9-10Faulty HDO action selection during fault auto resetting00: No action
1: Action

If fault auto reset function is valid, during fault auto resetting, fault reply action or not can be set via P9-10.

ParameterNameFactory defaultSetting range
P9-11Fault auto reset interval1.0s0.1s ~ 100.0s

The waiting time of the inverter from the fault alarm to auto reset.

ParameterNameFactory defaultSetting range
P9-12Input phase failure protection selection00: Invalid
1: Valid

KE300 series inverter has no input phase failure protection function at present, whatever P9-12 is set to 0 or 1, this function is invalid.

ParameterNameFactory defaultSetting range
P9-13Output phase failure protection selection10: Invalid
1: Valid

Select to protect output phase failure or not.

Fault record – fault types

ParameterNameRange
P9-14The first fault type0 ~ 50
P9-15The second fault type0 ~ 50
P9-16The third (last) fault type0 ~ 50

It is used to record the fault types of last three times: 0 indicates no fault, please refer to Chapter 8 for solutions.

Fault record – details of the last three faults

ParameterNameDescription
P9-17The third fault frequencyThe last fault frequency
P9-18The third fault currentThe last fault current
P9-19The third (last) fault bus voltageThe last fault bus voltage
P9-20The third fault type output terminal statusThe last fault type output terminal status, sequence: when the input terminal is ON, the corresponding binary bit is 1, when the input terminal is OFF, the corresponding binary bit is 0. All DI statuses are displayed as decimal numbers.
P9-21The third fault type output terminalThe last fault type output terminal status, sequence: when the input terminal is ON, the corresponding binary bit is 1, when the input terminal is OFF, the corresponding binary bit is 0. All DO statuses are displayed as decimal numbers.
P9-22The third fault inverter statusThe last fault inverter status
P9-23The third (last) fault power on timeThe last fault power on time
P9-24The third (last) fault running timeThe last fault running time
P9-27The second fault frequencySame as P9-17 ~ P9-24
P9-28The second fault currentSame as P9-17 ~ P9-24
P9-29The second fault bus voltageSame as P9-17 ~ P9-24
P9-30The second fault input terminal statusSame as P9-17 ~ P9-24
P9-31The second fault output terminal statusSame as P9-17 ~ P9-24
P9-32The second fault inverter statusSame as P9-17 ~ P9-24
P9-33The second fault power on timeSame as P9-17 ~ P9-24
P9-34The second fault running timeSame as P9-17 ~ P9-24
P9-37The first fault frequencySame as P9-17 ~ P9-24
P9-38The first fault currentSame as P9-17 ~ P9-24
P9-39The first fault bus voltageSame as P9-17 ~ P9-24
P9-40The first fault input terminal statusSame as P9-17 ~ P9-24
P9-41The first fault output terminal statusSame as P9-17 ~ P9-24
P9-42The first fault inverter statusSame as P9-17 ~ P9-24
P9-43The first fault power on timeSame as P9-17 ~ P9-24
P9-44The first fault running timeSame as P9-17 ~ P9-24
ParameterNameFactory defaultSetting range
P9-47Fault protection action selection 100000Units place – motor overload (E-11):
0: Coast to stop
1: Dec-to-stop
2: Keep running
Tens place – input phase failure (E-12) (same as units place)
Hundreds place – output phase failure (E-13) (same as units place)
Thousands place – external fault (E-14) (same as units place)
Ten thousands place – communication fault (E-15) (same as units place)
P9-48Fault protection action selection 200000Units place – reserved
Tens place – E²PROM W/R fault (E-21):
0: Coast to stop
1: Dec-to-stop
Hundreds place – reserved
Thousands place – reserved
Ten thousands place – running time arrival (E-26) (same as units place of P9-47)
P9-49Fault protection action selection 300000Units place – customized fault 1 (E-27) (same as units place of P9-47)
Tens place – customized fault 2 (E-28) (same as units place of P9-47)
Hundreds place – power-on time arrival (E-29) (same as P9-47 units place)
Thousands place – off load (E-30):
0: Coast to stop
1: Dec-to-stop
2: Deceleration to 7% of motor rated power, then keep running; run at setting frequency when no off-load
Ten thousands place – PID feedback lost when running (E-31) (same as units place of P9-47)
ParameterNameFactory defaultSetting range
P9-50Fault protection action selection 400000Units place – speed deviation oversize (E-42) (same as units place of P9-47)
Tens place – motor over speed (E-43) (same as units place of P9-47)
Hundreds place – reserved
Thousands place – reserved
Ten thousands place – reserved

When the selection is “Coast to stop”, the inverter shows E-** and stops directly.

When the selection is “Dec- to-stop”, the inverter shows A-** and decelerates to stop, then shows E-** after stopping.

When the selection is “keep running”, the inverter shows A-** and keeps running, the running frequency is set by P9-54.

ParameterNameFactory defaultSetting range
P9-54Running frequency selection continuously when fault00: Run at current running frequency
1: Run at setting frequency
2: Run at upper limit frequency
3: Run at lower limit frequency
4: Run at abnormal backup frequency
P9-55Abnormal backup frequency100.0%60.0% ~ 100.0%

When a fault happens during running and the fault process mode is keep running, the inverter shows A-** with the frequency set by P9-54.

When the inverter is running with the abnormal backup frequency, the value set by P9-55 corresponds to maximum frequency percentage.

ParameterNameFactory defaultSetting range
P9-59Instantaneous power-off action00: Invalid
1: Deceleration
2: Dec-to-stop
P9-60Instantaneous power-off recover judgment voltage90.0%80.0% ~ 100.0%
P9-61Instantaneous power-off voltage recover judgment time0.50s0.00s ~ 100.00s
P9-62Instantaneous power-off action judgment voltage80.0%60.0% ~ 100.0% (standard bus voltage)

The function is that, when instantaneous power off or voltage drops suddenly, the inverter will reduce output speed to decrease compensation voltage for DC bus which is generated by the load feedback energy, so that keep the inverter running.

P9-59=1: When instantaneous power off or voltage drops suddenly, the inverter decelerates, when bus voltage returns to normal, the inverter accelerates to the setting frequency and runs. Normal bus voltage lasts for longer than the time set by P9-61 means that bus voltage returns to normal.

P9-59=2: When instantaneous power off or voltage drops suddenly, the inverter decelerates to stop.

Diagram: Figure 6-23 Instantaneous stop action diagram

Diagram description (text version): Figure 6-23 Instantaneous power-off action: when the bus voltage drops below the action judgment voltage P9-62, the inverter decelerates (DEC time 3, then DEC time 4 below the recover judgment level P9-60). With P9-59 = 1 (deceleration), if the bus voltage recovers and stays above the recover level for the judgment time P9-61, the inverter re-accelerates to the original frequency (recover ACC time). With P9-59 = 2 (DEC to stop), the inverter decelerates to stop.

ParameterNameFactory defaultSetting range
P9-63Off-load protection selection00: Invalid
1: Valid
P9-64Off-load detection level10.0%0.0% ~ 100.0% (motor rated current)
P9-65Off-load detection time1.0s0.0s ~ 60.0s

If off-load protection function is valid, when the output current is smaller than off-load detection level P9-64, lasts for longer than off-load detection time P9-65, the output frequency will reduce to 7% of the rated frequency automatically. During off-load protection, if load recovers, the inverter will recover and run with the setting frequency automatically

Group PA PID Function

PID control is a common used method in process control, such as flow, pressure and temperature control.

The principle is firstly to detect the bias between preset/given value and feedback value, then calculate output frequency of inverter according to proportional gain, integral and differential time. Please refer to following figure.

Diagram: Figure 6-24 PID control diagram

Diagram description (text version): Figure 6-24 PID control: the PID preset value minus the filtered feedback value (filter F) is fed to the PID controller; its output goes through the control algorithm to the inverter output frequency driving the motor M and pump P; the measured process value returns as the feedback value.

ParameterNameFactory defaultSetting range
PA-00PID given source00: PA-01
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: Communication
6: Multi-step command
PA-01PID keypad given0.00.0 ~ PA-04 (PID given feedback range)

This parameter is used to select the given channel of PID target value

This value is an actual physical quantity. It must correspond to the measure range. For example, if the PID keypad given value is 0.3Mpa, PA-01 should be set to 3.0.

ParameterNameFactory defaultSetting range
PA-02PID feedback source00: AI1
1: AI2
2: Keypad potentiometer
3: AI1 − AI2
4: High speed pulse HDI
5: Communication
6: AI1 + AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)

These parameters are used to select PID given and feedback source.

Notice: Given value and feedback value of PID are percentage values.

100% of given value is corresponding to 100% of feedback value.

Given source and feedback source must not be same, otherwise PID will be malfunction.

ParameterNameFactory defaultSetting range
PA-03PID action direction00: Positive
1: Negative

0: Positive. When the feedback value is greater than the given value, output frequency will be decreased, such as tension control in winding application.

1: Negative. When the feedback value is greater than the given value, output frequency will be increased, such as tension control in unwinding application.

ParameterNameFactory defaultSetting range
PA-04PID given/feedback range100.0PA-01 (PID given through keypad) ~ 1000.0

PID given feedback range is a non-dimensional unit. It must correspond to the actual measure range. For example, if the measure range of the pressure meter is 1.0 Mpa, then this parameter should be set to 10.

ParameterNameFactory defaultSetting range
PA-05Proportional gain Kp120.00.0 ~ 100.0
PA-06Integration time Ti12.00s0.01s ~ 10.00s
PA-07Differential time Td10.000s0.00 ~ 10.000

Proportional gain Kp1: It decides the adjustment intensity of the whole PID regulator. The higher the Kp1 is, the stronger the adjustment intensity is. When this parameter is 100, indicating the deviation between PID feedback value and given value is 100%, the adjustment amplitude of the PID regulator on the output frequency command is maximum frequency.

Integration time Ti1: It decides the intensity of the integration adjustment of PID regulator. The shorter the integration time is, the stronger the adjustment intensity is. Integration time is the time within which the adjustment value reaches maximum frequency when the deviation between PID feedback value and given value is 100%.

Differential time Td1: It decides the intensity of the deviation change rate of PID regulator. The longer the differential time is, the stronger the adjustment intensity is. Differential time is the time within which if the feedback value changes 100%, the adjustment value reaches maximum frequency

ParameterNameFactory defaultSetting range
PA-08Cut-off frequency of PID reverse0.00Hz0.00 ~ P0-10 (maximum frequency)

In some situation, only when PID output frequency is negative (inverter reverse), PID can make given value and feedback value in a same status. But the reverse frequency cannot be too high for some applications. The reverse frequency upper limit is determined by PA-08.

ParameterNameFactory defaultSetting range
PA-09PID deviation limit0.0%0.0% ~ 100.0%

When the deviation between PID given value and feedback value is smaller than PA-09, PID stops adjustment. The output frequency is stable when the deviation is small, which is suitable for some close loop control applications.

ParameterNameFactory defaultSetting range
PA-10PID differential amplitude0.10%0.00% ~ 100.00%
PA-11PID given filter time0.00s0.00s ~ 650.00s

PID given filter time is the time that PID given value changes from 0.0% to 100.0%.

When PID given is changing, PID given value linearly changes according to the given filter time, so as to reduce the adverse effect of the system caused by the given sudden change.

ParameterNameFactory defaultSetting range
PA-12PID feedback filter time0.00s0.00s ~ 60.00s
PA-13PID output filter time0.00s0.00s ~ 60.00s

PA-12 is used to filter the PID feedback value, this filter can improve anti-interference capability of feedback value, but will bring the response performance of the process close loop system down.

PA-13 is used to filter the PID output frequency, this filter will reduce the sudden change of the inverter output frequency, but also will bring the response performance of the process close loop system down

ParameterNameFactory defaultSetting range
PA-15Proportional gain Kp220.00.0 ~ 100.0
PA-16Integration time Ti22.00s0.01s ~ 10.00s
PA-17Differential time Td20.000s0.00 ~ 10.000
PA-18PID parameter switching condition00: No switching
1: Switching via terminals
2: Automatic switching according to the deviation
PA-19PID parameter switching deviation 120.0%0.0% ~ PA-20
ParameterNameFactory defaultSetting range
PA-20PID parameter switching deviation 280.0%PA-19 ~ 100.0%

In some applications, one group PID parameter is not enough, different PID parameters would be adopted according to the situation.

The function codes are used to switch two groups PID parameter. The setting mode of the regulator parameters PA-15~PA-17 is similar as PA-05~PA-07’s.

Two groups PID parameter can be switched via DI terminal, or switched according to PID deviation automatically.

When selection is automatic switching: when the deviation absolute value between given and feedback is smaller than PA-19 (PID parameter switching deviation 1), PID parameter selection is group 1. When the deviation absolute value between given and feedback is bigger than PA-20 (PID parameter switching deviation 2), PID parameter selection is group 2. When the deviation absolute value between given and feedback is between PA-19 and PA-20, PID parameter is the linear interpolation of two groups PID parameter, showed as figure 6-25.

Diagram: Figure 6-25 PID parameter switching diagram

Diagram description (text version): Figure 6-25 PID parameter switching: when the PID deviation is below PA-19 the controller uses PI parameter set 1 (PA-05, PA-06, PA-07); above PA-20 it uses set 2 (PA-15, PA-16, PA-17); between PA-19 and PA-20 the parameters change linearly from set 1 to set 2.

ParameterNameFactory defaultSetting range
PA-21PID initial value0.0%0.0% ~ 100.0%
PA-22PID initial value holding time0.00s0.00s ~ 360.00s

When starting, PID output is PID initial value (PA-21), lasts for PID initial value holding time (PA-22), PID starts close-loop regulate calculating

Diagram: Figure 6-26 PID initial value function diagram

Diagram description (text version): Figure 6-26 PID initial value: after start the output frequency ramps to the PID initial value PA-21 and is held there for the holding time PA-22; after that the PID regulation takes over and the frequency follows the PID output.

ParameterNameFactory defaultSetting range
PA-23Forward maximum value between two output deviations1.00%0.00% ~ 100.00%
PA-24Reverse maximum value between two output deviations1.00%0.00% ~ 100.00%

This function is used to limit the difference between PID output two bats (2ms/bat), so as to against PID output changing too fast, make the inverter run stably.

PA-23 and PA-24 correspond to the maximum of the output deviation absolute value when forward and reverse, respectively.

ParameterNameFactory defaultSetting range
PA-25PID integration attribute00Units place – integration separate:
0: Invalid
1: Valid
Tens place – stop integrating or not after output reaches limit:
0: Continue integrating
1: Stop integrating

Integration separation:

If integration separation is valid, when multifunctional digital DI integration pause (function 22) is valid, PID integration stop calculating, PID is only valid when proportional and differential action.

When integration separation is invalid, whatever multifunctional digital DI is valid or not, integration separation is invalid.

Stop integrating or not after output reach limit:

After PID calculation output reaches the maximum or minimum, whether stop integral action or not can be selected. If the selection is stop integrating, PID integration will stop calculating, which may help to reduce PID overshoot.

ParameterNameFactory defaultSetting range
PA-26PID feedback lost detection value0.0%0.0%: no judgment for feedback lost
0.1% ~ 100.0%
PA-27PID feedback lost detection time1.0s0.0s ~ 20.0s

The parameters are used to judge whether PID feedback lost or not.

When PID feedback is smaller than feedback lost detection value (PA-26), lasts for longer than PID feedback lost detection time (PA-27), the inverter alarms fault E-31, and handles according to the chose fault process mode.

ParameterNameFactory defaultSetting range
PA-28PID stop calculation10: No calculation when stop
1: Calculation when stop

This parameter is used to select PID stop status & whether PID continues calculating or not. For normal applications, PID should stop calculating when stop

Słowa kluczowe

Micno KE300, opis parametrów, parameter description, P9, PA, zabezpieczenia, protection, przeciążenie, overload, auto reset, rejestr błędów, fault record, PID, sprzężenie zwrotne, feedback