5. Function Parameter List – Part 3 (PA–A2, U0)
Streszczenie: Tabela parametrów funkcyjnych KE600 (część 3 z 3): grupy PA–PP, A0 i A2 (PID, wobble, PLC, komunikacja, zarządzanie parametrami, moment, silnik 2) oraz tabela monitorowania U0 – zakresy nastaw, wartości fabryczne i możliwość zmiany.
EN: KE600 function parameter list (part 3 of 3): groups PA–PP, A0 and A2 (PID, wobble, PLC, communication, parameter management, torque, motor 2) and the U0 monitoring table – setting ranges, factory defaults and modification attributes.
Dotyczy: falownik wektorowy z zamkniętą pętlą Micno KE600 (zasilanie 3AC 220 V, 3AC 380 V, 3AC 660 V; moce 1,5–630 kW)
Źródło: dokumentacja producenta (Micno KE600 Series Inverter User Manual); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt
5.1 Basic Function Parameter Table (Continued)
Kolumna „Modify”: ○ – parameter can be modified in stop and running status; ◎ – cannot be modified in running status; ● – actual detected value, cannot be modified.
PA Group: PID Function
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| PA-00 | PID given source | 0: PA-01 1: AI1 2: AI2 3: Keypad potentiometer 4: High speed pulse HDI 5: Communication 6: Multi-step command | 0 | ○ |
| PA-01 | PID given through keypad | 0.0 ~ PA-04 (PID given feedback range) | 0.0 | ○ |
| PA-02 | PID feedback source | 0: AI1 1: AI2 2: Keypad potentiometer 3: AI1 − AI2 4: High speed pulse HDI 5: Communication 6: AI1 + AI2 7: MAX (|AI1|, |AI2|) 8: MIN (|AI1|, |AI2|) | 0 | ○ |
| PA-03 | PID action direction | 0: Positive 1: Negative | 0 | ○ |
| PA-04 | PID given feedback range | PA-01 (PID given through keypad) ~ 1000.0 | 100.0 | ○ |
| PA-05 | Proportional gain Kp1 | 0.0 ~ 100.0 | 20.0 | ○ |
| PA-06 | Integration time Ti1 | 0.01s ~ 10.00s | 2.00s | ○ |
| PA-07 | Differential time Td1 | 0.000s ~ 10.000s | 0.000s | ○ |
| PA-08 | Cutoff frequency of PID reverse | 0.00 ~ P0-10 (maximum frequency) | 0.00Hz | ○ |
| PA-09 | PID deviation limit | 0.0% ~ 100.0% | 0.0% | ○ |
| PA-10 | PID differential amplitude | 0.00% ~ 100.00% | 0.10% | ○ |
| PA-11 | PID given filter time | 0.00 ~ 650.00s | 0.00s | ○ |
| PA-12 | PID feedback filter time | 0.00 ~ 60.00s | 0.00s | ○ |
| PA-13 | PID output filter time | 0.00 ~ 60.00s | 0.00s | ○ |
| PA-14 | Reserved | – | – | ○ |
| PA-15 | Proportional gain Kp2 | 0.0 ~ 100.0 | 20.0 | ○ |
| PA-16 | Integration time Ti2 | 0.01s ~ 10.00s | 2.00s | ○ |
| PA-17 | Differential time Td2 | 0.000s ~ 10.000s | 0.000s | ○ |
| PA-18 | PID parameter switching condition | 0: No switching 1: Switching via terminals 2: Automatic switching according to the deviation | 0 | ○ |
| PA-19 | PID parameter switching deviation 1 | 0.0% ~ PA-20 | 20.0% | ○ |
| PA-20 | PID parameter switching deviation 2 | PA-19 ~ 100.0% | 80.0% | ○ |
| PA-21 | PID initial value | 0.0% ~ 100.0% (printed in the source as “00.0%”) | 0.0% | ○ |
| PA-22 | PID initial value holding time | 0.00 ~ 360.00s | 0.00s | ○ |
| PA-23 | Forward maximum value between two output deviation | 0.00% ~ 100.00% | 1.00% | ○ |
| PA-24 | Reverse maximum value between two output deviation | 0.00% ~ 100.00% | 1.00% | ○ |
| PA-25 | PID integration attribute | Units place: integration separate 0: Invalid 1: Valid Tens place: stop integrating or not after output reaches limit 0: Keep integrating 1: Stop integrating | 00 | ○ |
| PA-26 | PID feedback lost detection value | 0.0%: no judgment for feedback lost 0.1% ~ 100.0% | 0.0% | ○ |
| PA-27 | PID feedback lost detection time | 0.0s ~ 20.0s | 0.0s | ○ |
| PA-28 | PID stop calculation | 0: No calculation when stop 1: Calculation when stop | 1 | ○ |
Pb Group: Wobble Frequency, Fixed Length, Counting
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| Pb-00 | Wobble frequency setting mode | 0: Relative to center frequency 1: Relative to maximum frequency | 0 | ○ |
| Pb-01 | Wobble frequency amplitude | 0.0% ~ 100.0% | 0.0% | ○ |
| Pb-02 | Sudden jump frequency amplitude | 0.0% ~ 50.0% | 0.0% | ○ |
| Pb-03 | Wobble frequency cycle | 0.1s ~ 3000.0s | 10.0s | ○ |
| Pb-04 | Triangular wave rise time of wobble frequency | 0.1% ~ 100.0% | 50.0% | ○ |
| Pb-05 | Setting length | 0m ~ 65535m | 1000m | ○ |
| Pb-06 | Actual length | 0m ~ 65535m | 0m | ○ |
| Pb-07 | Number of pulses per meter | 0.1 ~ 6553.5 | 100.0 | ○ |
| Pb-08 | Setting count value | 1 ~ 65535 | 1000 | ○ |
| Pb-09 | Designated count value | 1 ~ 65535 | 1000 | ○ |
PC Group: Multi-step Command and Simple PLC
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| PC-00 | Multi-step command 0 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-01 | Multi-step command 1 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-02 | Multi-step command 2 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-03 | Multi-step command 3 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-04 | Multi-step command 4 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-05 | Multi-step command 5 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-06 | Multi-step command 6 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-07 | Multi-step command 7 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-08 | Multi-step command 8 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-09 | Multi-step command 9 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-10 | Multi-step command 10 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-11 | Multi-step command 11 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-12 | Multi-step command 12 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-13 | Multi-step command 13 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-14 | Multi-step command 14 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-15 | Multi-step command 15 | -100.0% ~ 100.0% | 0.0% | ○ |
| PC-16 | Simple PLC running mode | 0: Stop after one cycle 1: Keep last frequency after one cycle 2: Circular running | 0 | ○ |
| PC-17 | Simple PLC storage selection when power-down | Units place: storage selection when power-off 0: Not store 1: Store Tens place: storage selection when stop 0: Not store 1: Store | 00 | ○ |
| PC-18 | Phase 0 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-19 | Phase 0 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-20 | Phase 1 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-21 | Phase 1 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-22 | Phase 2 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-23 | Phase 2 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-24 | Phase 3 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-25 | Phase 3 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-26 | Phase 4 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-27 | Phase 4 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-28 | Phase 5 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-29 | Phase 5 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-30 | Phase 6 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-31 | Phase 6 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-32 | Phase 7 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-33 | Phase 7 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-34 | Phase 8 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-35 | Phase 8 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-36 | Phase 9 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-37 | Phase 9 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-38 | Phase 10 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-39 | Phase 10 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-40 | Phase 11 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-41 | Phase 11 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-42 | Phase 12 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-43 | Phase 12 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-44 | Phase 13 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-45 | Phase 13 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-46 | Phase 14 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-47 | Phase 14 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-48 | Phase 15 running time | 0.0s (m) ~ 6500.0s (m) | 0.0s (m) | ○ |
| PC-49 | Phase 15 ACC/DEC time selection | 0 ~ 3 | 0 | ○ |
| PC-50 | Timing unit (simple PLC mode) | 0: s (second) 1: m (minute) | 0 | ○ |
| PC-51 | Multi-step command 0 given mode | 0: PC-00 1: AI1 2: AI2 3: Keypad potentiometer 4: High speed pulse HDI 5: PID control 6: Keypad setting frequency (P0-08), can be modified via UP/DN | 0 | ○ |
Pd Group: Communication Parameters
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| Pd-00 | Baud rate | 0: 300BPS 1: 600BPS 2: 1200BPS 3: 2400BPS 4: 4800BPS 5: 9600BPS 6: 19200BPS 7: 38400BPS | 5 | ○ |
| Pd-01 | Data format | 0: No parity check (8-N-2) 1: Even parity check (8-E-1) 2: Odd parity check (8-O-1) 3: No parity check (8-N-1) | 0 | ○ |
| Pd-02 | Local address | 1 ~ 247, 0 is broadcast address | 1 | ○ |
| Pd-03 | Response delay | 0ms ~ 20ms | 2 | ○ |
| Pd-04 | Communication timeout time | 0.0 (invalid) 0.1s ~ 60.0s | 0.0 | ○ |
| Pd-05 | Communication protocol selection | 0: Non-standard MODBUS protocol 1: Standard MODBUS protocol | 1 | ○ |
| Pd-06 | Communication read current resolution | 0: 0.01A 1: 0.1A | 0 | ○ |
PE Group: Reserved Function
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| FE-00 (PE-00) | Reserved | – | – | ○ |
PP Group: Function Code Management
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| PP-00 | User password | 0 ~ 65535 | 0 | ○ |
| PP-01 | Parameter initialization | 0: No action 1: Restore factory default, but not including motor parameters 2: Clear the record | 0 | ◎ |
| PP-02 | Function parameter group display selection | Units place: U0 group display selection 0: No display 1: Display Tens place: A0 group display selection 0: No display 1: Display | 00 | ◎ |
| PP-03 | Reserved | – | – | ● |
| PP-04 | Function code modification attribute | 0: Disable 1: Enable | 0 | ○ |
A0 Group: Torque Control Parameters
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| A0-00 | Speed/torque control mode selection | 0: Speed control 1: Torque control | 0 | ◎ |
| A0-01 | Torque setting source selection in torque control mode | 0: Keypad (A0-03) 1: AI1 2: AI2 3: Keypad potentiometer 4: High speed pulse HDI 5: Communication 6: Min (AI1, AI2) 7: Max (AI1, AI2) | 0 | ◎ |
| A0-03 | Torque setting through keypad in torque control mode | -200.0% ~ 200.0% | 150.0% | ○ |
| A0-04 | Torque filter time | 0.00s ~ 10.00s | 0.00s | ○ |
| A0-05 | Forward maximum frequency in torque control mode | 0.00Hz ~ P0-10 (maximum frequency) | 50.00Hz | ○ |
| A0-06 | Reverse maximum frequency in torque control mode | 0.00Hz ~ P0-10 (maximum frequency) | 50.00Hz | ○ |
| A0-07 | Acc time in torque control mode | 0.00s ~ 36000s | 0.00s | ○ |
| A0-08 | Dec time in torque control mode | 0.00s ~ 36000s | 0.00s | ○ |
A2 Group: Motor 2 Parameters
| Function code | Name | Detailed instruction | Factory default | Modify |
|---|---|---|---|---|
| A2-00 | Motor type | 0: Common asynchronous motor 1: Variable frequency asynchronous motor | 0 | ◎ |
| A2-01 | Rated power | 0.1kW ~ 1000.0kW | Model dependent | ◎ |
| A2-02 | Rated voltage | 1V ~ 2000V | Model dependent | ◎ |
| A2-03 | Rated current | 0.01A ~ 655.35A (inverter power ≤ 55kW) 0.1A ~ 6553.5A (inverter power > 55kW) | Model dependent | ◎ |
| A2-04 | Rated frequency | 0.00Hz ~ P0-10 (max. frequency) | Model dependent | ◎ |
| A2-05 | Rated speed | 1rpm ~ 36000rpm | Model dependent | ◎ |
| A2-06 | Stator resistance | 0.001Ω ~ 65.535Ω (inverter power ≤ 55kW) 0.0001Ω ~ 6.5535Ω (inverter power > 55kW) | Motor parameter | ◎ |
| A2-07 | Rotor resistance | 0.001Ω ~ 65.535Ω (inverter power ≤ 55kW) 0.0001Ω ~ 6.5535Ω (inverter power > 55kW) | Motor parameter | ◎ |
| A2-08 | Leakage inductance | 0.01mH ~ 655.35mH (inverter power ≤ 55kW) 0.001mH ~ 65.535mH (inverter power > 55kW) | Motor parameter | ◎ |
| A2-09 | Mutual inductance | 0.01mH ~ 655.35mH (inverter power ≤ 55kW) 0.001mH ~ 65.535mH (inverter power > 55kW) | Motor parameter | ◎ |
| A2-10 | No-load current | 0.01A ~ P1-03 (rated current) (inverter power ≤ 55kW) 0.1A ~ P1-03 (rated current) (inverter power > 55kW) | Motor parameter | ◎ |
| A2-11 | Parameters autotuning | 0: No action 1: Static autotuning 2: Rotation autotuning | 0 | ◎ |
| A2-27 | Encoder resolution | 1 ~ 10000 | 1000 | ◎ |
| A2-28 | Encoder type | 0: ABZ incremental encoder | 0 | ● |
| A2-30 | Phase-sequence of ABZ incremental encoder | 0: Forward 1: Reverse | 0 | ◎ |
| A2-36 | Detection of PG cables disconnect | 0.0: no detection 0.1 ~ 10.00s | 0.0 | ◎ |
| A2-38 | Speed loop proportional gain 1 | 1 ~ 100 | 25 | ○ |
| A2-39 | Speed loop integration time 1 | 0.01s ~ 10.00s | 0.50s | ○ |
| A2-40 | Low switching frequency | 0.00 ~ P2-05 | 5.00Hz | ○ |
| A2-41 | Speed loop proportional gain 2 | 1 ~ 100 | 20 | ○ |
| A2-42 | Speed loop integration time 2 | 0.01s ~ 10.00s | 1.00s | ○ |
| A2-43 | High switching frequency | P2-02 ~ P0-10 (max. frequency) | 10.00Hz | ○ |
| A2-44 | Vector control slip compensation coefficient | 50% ~ 200% | 100% | ○ |
| A2-45 | Speed loop filter time | 0.000s ~ 0.100s | 0.000s | ○ |
| A2-46 | Vector control over excitation gain | 0 ~ 200 | 64 | ○ |
| A2-47 | Torque upper limit source selection in speed control mode | 0: Set by A2-48 1: AI1 2: AI2 3: Keypad potentiometer 4: High speed pulse HDI 5: Communication 6: Min (AI1, AI2) 7: Max (AI1, AI2) Full scale of selections 1–7 corresponds to A2-48 | 0 | ○ |
| A2-48 | Torque upper limit digital setting | 0.0% ~ 200.0% | 150.0% | ○ |
| A2-51 | Proportional gain of excitation regulation | 0 ~ 6000 | 2000 | ○ |
| A2-52 | Integral gain of excitation regulation | 0 ~ 6000 | 1300 | ○ |
| A2-53 | Proportional gain of torque regulation | 0 ~ 6000 | 2000 | ○ |
| A2-54 | Integral gain of torque regulation | 0 ~ 6000 | 1300 | ○ |
| A2-61 | Motor 2 control mode | 0: V/f 1: Sensorless vector control | 0 | ◎ |
5.2 Monitoring Parameter Table
U0 Group: Basic Monitoring Parameters
| Function code | Name | Minimum unit |
|---|---|---|
| U0-00 | Running frequency (Hz) | 0.01Hz |
| U0-01 | Setting frequency (Hz) | 0.01Hz |
| U0-02 | DC bus voltage (V) | 0.1V |
| U0-03 | Output voltage (V) | 1V |
| U0-04 | Output current (A) | 0.01A |
| U0-05 | Output power (kW) | 0.1kW |
| U0-06 | Output torque (%) | 0.1% |
| U0-07 | DI input status | 1 |
| U0-08 | DO output status | 1 |
| U0-09 | AI1 voltage (V) | 0.01V |
| U0-10 | AI2 voltage (V) | 0.01V |
| U0-11 | Radiator temperature | 1 °C |
| U0-12 | Count value | 1 |
| U0-13 | Length value | 1 |
| U0-14 | Load speed | 1 |
| U0-15 | PID setting | 1 |
| U0-16 | PID feedback | 1 |
| U0-17 | PLC phase | 1 |
| U0-18 | HDI input pulse frequency (Hz) | 0.01kHz |
| U0-19 | Feedback speed (unit 0.1Hz) | 0.1Hz |
| U0-20 | Remain running time | 0.1 min |
| U0-21 | AI1 voltage before calibration | 0.001V |
| U0-22 | AI2 voltage before calibration | 0.001V |
| U0-23 | Keypad potentiometer voltage before calibration | 0.001V |
| U0-24 | Linear velocity | 1 m/min |
| U0-25 | Current power-on time | 1 min |
| U0-26 | Current running time | 0.1 min |
| U0-27 | HDI input pulse frequency | 1Hz |
| U0-28 | Communication setting value | 0.01% |
| U0-29 | Encoder feedback frequency | 0.01Hz |
| U0-30 | Main frequency A display | 0.01Hz |
| U0-31 | Auxiliary frequency B display | 0.01Hz |
| U0-32 | Reserved | – |
| U0-33 | Reserved | – |
| U0-34 | Motor temperature | 1 °C |
| U0-35 | Target torque (%) | 0.1% |
| U0-36 | Reserved | 1 |
| U0-37 | Power factor angle | 0.1° |
| U0-38 | ABZ position | 1 |
| U0-39 | Reserved | – |
| U0-40 | Reserved | – |
| U0-41 | DI input status visual display | 1 |
| U0-42 | DO input status visual display | 1 |
| U0-43 | DI function status display 1 (function 01 – function 40) | 1 |
| U0-44 | DI function status visual display 2 (function 41 – function 80) | 1 |
| U0-59 | Setting frequency (%) | 0.01% |
| U0-60 | Running frequency (%) | 0.01% |
| U0-61 | Inverter status | 1 |
Słowa kluczowe
Micno KE600, lista parametrów, parameter list, PA–A2, U0, wartość fabryczna, factory default, zakres nastaw, setting range