6. Parameter Description – Part 2 (Groups P1–P3)

Streszczenie: Opis parametrów KE600 (część 2 z 8): parametry silnika 1, enkoder i autotuning, sterowanie wektorowe (pętla prędkości, limit momentu, regulatory wzbudzenia i momentu) oraz sterowanie V/F.
EN: KE600 parameter description (part 2 of 8): motor 1 parameters, encoder and autotuning, vector control (speed loop, torque limit, excitation and torque regulators) and V/F control.

Dotyczy: falownik wektorowy z zamkniętą pętlą Micno KE600 (zasilanie 3AC 220 V, 3AC 380 V, 3AC 660 V; moce 1,5–630 kW)
Źródło: dokumentacja producenta (Micno KE600 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt

Group P1 Motor 1 Parameters

ParameterNameFactory defaultSetting range
P1-00Motor type00: Common asynchronous motor
1: Variable frequency asynchronous motor
P1-01Motor rated powerModel dependent0.1kW ~ 1000.0kW
P1-02Motor rated voltageModel dependent1V ~ 2000V
P1-03Motor rated currentModel dependent0.01A ~ 655.35A (inverter power ≤ 55kW)
0.1A ~ 6553.5A (inverter power > 55kW)
P1-04Motor rated frequencyModel dependent0.01Hz ~ P0-10 (maximum frequency)
P1-05Motor rated speedModel dependent1rpm ~ 65535rpm
  1. Please set the parameters correctly according to the motor nameplate.
  2. In order to achieve superior control performance, please perform motor parameters autotuning. The accuracy of autotuning is closely related to the correct setting of the rated motor parameters.
ParameterNameFactory defaultSetting range
P1-06Motor stator resistanceModel dependent0.001Ω ~ 65.535Ω (inverter power ≤ 55kW)
0.0001Ω ~ 6.5535Ω (inverter power > 55kW)
P1-07Motor rotor resistanceModel dependent0.001Ω ~ 65.535Ω (inverter power ≤ 55kW)
0.0001Ω ~ 6.5535Ω (inverter power > 55kW)
P1-08Motor leakage inductanceModel dependent0.01mH ~ 655.35mH (inverter power ≤ 55kW)
0.001mH ~ 65.535mH (inverter power > 55kW)
P1-09Motor mutual inductanceModel dependent0.1mH ~ 6553.5mH (inverter power ≤ 55kW)
0.01mH ~ 655.35mH (inverter power > 55kW)
P1-10Motor current without loadModel dependent0.01A ~ P1-03 (inverter power ≤ 55kW)
0.1A ~ P1-03 (inverter power > 55kW)

P1-06 ~ P1-10 are motor parameters, which cannot be found on the motor nameplate, and are obtained via the inverter autotuning. The static autotuning only can obtain P1-06 ~ P1-08. The rotation autotuning not only can obtain P1-06 ~ P1-10, but also can get current loop PI parameter, etc.

When P1-01 or P1-02 changed, the values of P1-06 ~ P1-10 will be changed automatically, and restore

P1-06 ~ P1-10 as standard Y series motor parameters.

If motor parameters autotuning failed in the site, please input the related parameters provided by the motor manufacturer.

ParameterNameFactory defaultSetting range
P1-11Motor parameters autotuning00: No operation
1: Static autotuning
2: Rotation autotuning

0: No operation, prohibit motor parameter autotuning.

1: Motor parameter static autotuning, suitable for the applications which the asynchronous motor is not easy to disconnect with the load, and cannot make rotation autotuning.

Before static autotuning, please set the motor type and motor parameters (P1-00 ~ P1-05) correctly. The inverter can obtain P1-06 ~ P1-08 via static autotuning.

Action description: Set the function code to be 1, the keypad displays “TUNE”, then press RUN key, the inverter will make static autotuning.

2: Motor parameter rotation autotuning

To ensure the dynamic control performance of inverter, please select rotation autotuning. During the rotation autotuning, the motor must be disconnected with the load (i.e. no-load).

During rotation autotuning, the inverter will make static autotuning at first, and then accelerates to 80% motor rated frequency according to acceleration time P0-17, holding for a while, at last decelerates to stop according to deceleration time P0-18 and finish autotuning.

Before rotation autotuning, please set motor type and motor parameters P1-00 ~ P1-05, during rotation autotuning, the inverter can obtain P1-06~P1-10, vector control current loop PI parameters P2-13 ~ P2-16.

Action description: Set the function code to 2, the keypad displays “TUNE”, then press RUN key, the inverter will make rotation autotuning.

Note: Autotuning is valid only on keypad operation mode, cannot make autotuning under terminal and communication operation modes.

ParameterNameFactory defaultSetting range
P1-27Encoder resolution10240 ~ 10000

Set the pulse quantity while the motor run one cycle.

Under the close-loop vector control mode, the encoder resolution has to be set correctly, otherwise, the motor cannot run normally.

ParameterNameFactory defaultSetting range
P1-28Encoder type00: ABZ incremental encoder

KE600 is only suitable for ABZ incremental encoder.

ParameterNameFactory defaultSetting range
P1-30Phase-sequence of ABZ incremental encoder00: Forward
1: Reverse

To set the phase-sequence of encoder A, B signal

ParameterNameFactory defaultSetting range
P1-36Detection time of PG cables disconnection0.00.0: no detection
0.1 ~ 10.00s

To set the detection time of encoder cables disconnection, if the set time is 0.0s, the inverter will not detect whether the encoder cable is disconnected or not.

While the encoder cables disconnect, and the time of duration is more than P1-36, the inverter will give failure information of “E-20”.

Group P2 Vector Control Parameters

Group P2 is valid only for vector control. That is to say, when P0-01=0 or 1, it is valid, and when P0-01=2, it is invalid.

ParameterNameFactory defaultSetting range
P2-00Speed loop proportional gain 1301 ~ 100
P2-01Speed loop integration time 10.50s0.01s ~ 10.00s
P2-02Low switching frequency5.00Hz0.00 ~ P2-05
P2-03Speed loop proportional gain 2201 ~ 100
P2-04Speed loop integration time 21.00s0.01s ~ 10.00s
P2-05High switching frequency10.00HzP2-02 ~ P0-10 (maximum frequency)

P2-00 and P2-01 are PI adjustment parameters when the running frequency is lower than low switching frequency (P2-02). P2-03 and P2-04 are PI adjustment parameters when the running frequency is higher than high switching frequency (P2-05). PI parameter of frequency channel between low switching frequency and high switching frequency is linear switching between two groups of PI parameters, as shown in the figure below:

Diagram: Figure 6-2 PI parameter diagram

Diagram description (text version): Figure 6-2 PI parameter diagram: below the low switching frequency P2-02 the speed loop uses PI parameters P2-00/P2-01; above the high switching frequency P2-05 it uses P2-03/P2-04; between P2-02 and P2-05 the PI parameters change linearly from the first to the second set.

The speed dynamic response characteristics of the vector control can be adjusted by setting the proportional coefficient and integration time of the speed regulator.

Increasing the proportional gain or reducing the integration time can accelerate the dynamic response of the speed loop. However, if the proportional gain is too large or the integration time is too short, it will cause the oscillation of the system.

If factory default cannot meet the requirements, the relevant parameter values can be subject to fine tuning.

Increase the proportional gain while ensuring no oscillation to the system, and then reduce the integration time to ensure that the system has quick response characteristics and small overshoot.

Caution: Improper PI parameter setting may cause too large speed overshoot. Voltage fault may occur when the overshoot drops.

ParameterNameFactory defaultSetting range
P2-06Vector control slip compensation coefficient100%50% ~ 200%

For sensorless vector control, this parameter is used to adjust the speed stabilizing precision of the motor. When the speed is too low due to heavy load of motor, this parameter needs to be enlarged, vice versa.

ParameterNameFactory defaultSetting range
P2-07Speed loop filter time0.000s0.000s ~ 0.100s

Under vector control mode, the output of speed loop regulator is torque current command. This parameter is used to filter the torque command. This parameter needs no adjustment generally and this filter time can be increased in case of huge speed fluctuation. In case of oscillation of motor, this parameter should be reduced properly.

The speed loop filter time is low, and the inverter output torque may fluctuate greatly, but the response is quick.

ParameterNameFactory defaultSetting range
P2-08Vector control over excitation gain640 ~ 200

During deceleration, over excitation control can suppress bus voltage increase, avoid over voltage fault.

The bigger over excitation gain is, the better the suppression result is.

For the application which over voltage fault happens frequently during deceleration, the over excitation gain needs to be increased. But the current would be increased if the over excitation is too bigger, so you need to set the suitable over excitation gain.

For the small inertia situation, voltage doesn’t increase during motor deceleration, please set over excitation gain to 0. For the application with braking resistor, please also set over excitation gain to 0.

ParameterNameFactory defaultSetting range
P2-09Torque upper limit source under speed control mode00: P2-10
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: Communication
P2-10Torque upper limit digital setting150.0%0.0% ~ 200.0%

In the speed control mode, the maximum of the inverter output torque is controlled by the torque upper limit source.

P2-09 is used to select the setting source of torque upper limit. When setting via the analog value, high speed pulse HDI, communication, 100% of the relevant setting corresponds to P2-10, and 100% of P2-10 is the inverter rated torque

ParameterNameFactory defaultSetting range
P2-11Optimum model selection of sensorless vector control00: No optimization
1: Torque linearity optimization
2: Speed stability optimization

While the torque control linearity is higher requested, set it to be 1, and while the speed stability is higher requested, set it to be 2.

ParameterNameFactory defaultSetting range
P2-13Proportional gain of excitation regulation20000 ~ 20000
P2-14Integral gain of excitation regulation13000 ~ 20000
P2-15Proportional gain of torque regulation20000 ~ 20000
P2-16Integral gain of torque regulation13000 ~ 20000

PI regulation parameters of vector control, the parameters will be got automatically after autotunning, in normal condition, they are unnecessary to be modified.

Note: if the PI gain values are set too big, it will cause the control be oscillation, while the current oscillation or torque fluctuation is bigger, the proportional gain and the Integral gain should be decreased manually.

Group P3 V/F Control Parameters

This group of function code is enabled only for V/F control (P0-01=2) and is invalid for vector control.

V/F control is applicable for the general loads such as fan and pump or the applications where one inverter drives multiple motors or the inverter power is one level lower or higher than the motor power.

ParameterNameFactory defaultSetting range
P3-00V/F curve setting00: Linear V/F curve
1: Multiple-point V/F curve
2: Square V/F curve
3: 1.2 power V/F
4: 1.4 power V/F
6: 1.6 power V/F
8: 1.8 power V/F

0: Linear V/F curve. It is suitable for common constant torque load.

1: Multiple-point V/F curve. It is suitable for the special loads such as dehydrator and centrifugal machine.

2: Square V/F curve. It is suitable for the centrifugal loads such as fan and pump.

3~8: VF curve between linear VF and square VF.

ParameterNameFactory defaultSetting range
P3-01Torque boostModel dependent0.0% ~ 30%
P3-02Cut-off frequency of torque boost50.00Hz0.00Hz ~ P0-10 (maximum frequency)

To compensate the low frequency torque characteristics of V/F control, it can boost the inverter output voltage during low frequency. If the torque boost is set to too large, the motor may be over heat, and the inverter may be over current.

Adjust this parameter according to the different loads. Increase this parameter for heavy load, reduce it for light load.

When the torque boost is set to 0.0, the inverter will adopt auto torque boost.

Cut-off frequency of torque boost: Under this frequency, the torque boost is valid. If it exceeds this setting frequency, the torque boost is invalid. Refer to Figure 6-3 for details.

Diagram: Figure 6-3 Manual torque boost diagram

Diagram description (text version): Figure 6-3 Manual torque boost: output voltage versus output frequency. With manual torque boost the V/F line starts at the boost voltage V1 at 0 Hz instead of 0 V and rises linearly; above the cut-off frequency f1 the curve joins the normal V/F line, reaching the maximum output voltage Vb at the rated running frequency fb (dashed line: V/F curve without boost).

ParameterNameFactory defaultSetting range
P3-03V/F frequency point 10.00Hz0.00Hz ~ P3-05
P3-04V/F voltage point 10.0%0.0% ~ 100.0%
P3-05V/F frequency point 20.00HzP3-03 ~ P3-07
P3-06V/F voltage point 20.0%0.0% ~ 100.0%
P3-07V/F frequency point 30.00HzP3-05 ~ P1-04 (motor rated frequency; the source says “motor rated power”)
P3-08V/F voltage point 30.0%0.0% ~ 100.0%

Multi-step V/F curve is defined by P3-03 to P3-08.

The curve of multi point V/F is generally set according to the load characteristics of the motor.

  • Caution: V1<V2<V3 and F1<F2<F3. The voltage corresponding to low frequency should not be set too high, otherwise it may cause motor overheat or inverter fault.

Diagram: Figure 6-4 V/F curve setting diagram

Diagram description (text version): Multi-point V/F curve: voltage versus frequency through three user points (f1, V1), (f2, V2), (f3, V3) set by P3-03…P3-08, then rising to 100% voltage at the rated frequency fb and staying constant above it. Frequencies and voltages must increase from point 1 to point 3.

ParameterNameFactory defaultSetting range
P3-09V/F slip compensation gain0.0%0% ~ 200.0%

It is valid only for V/F control.

Setting this parameter can compensate the slip of motor speed caused by the load increases, and makes the motor speed stably when the load changes.

V/F slip compensation gain set to 100% means the slip compensation of the motor with rated load is the motor rated slip, which can be calculated according to motor rated power and motor rated speed automatically.

Slip gain adjustment can refer to the following principle: When the load is rated load, the motor speed is basically the same as the target speed. When the values are different, please adjust this gain properly.

ParameterNameFactory defaultSetting range
P3-10V/F over-excitation gain640 ~ 200

During deceleration, over excitation control can suppress bus voltage increase, avoid over voltage fault.

The bigger over excitation gain is, the better suppression result is.

For the application which over voltage fault happens frequently during deceleration, the over excitation gain needs to be increased. But the current would be increased if the over excitation is too bigger, so you need to set the suitable over excitation gain.

For the small inertia situation, voltage doesn’t increase during motor deceleration, please set over excitation gain to 0. For the application with braking resistor, please also set over excitation gain to 0.

ParameterNameFactory defaultSetting range
P3-11V/F oscillation suppression gainModel dependent0 ~ 100

Set the gain as small as possible on the premise that there is effective oscillation suppression measure, which can avoid the affect causing to VF running. Set the gain to 0 when the motor has no oscillation. Only when the motor has obvious oscillation, this gain can be increased properly. The bigger the gain is, the better oscillation suppression result will be.

When using this function, please make sure the motor rated current and no load current parameters are accurate, otherwise V/F oscillation suppression result would be bad.