13. Homing

Streszczenie: Ekran Homing: ustawienie parametrów bazowania (limity programowe, metoda, prędkości, przyspieszenie, offset), uruchomienie testowego bazowania i zapis do pamięci flash.
EN: Homing screen: homing parameters, test homing and saving to flash.

Dotyczy: program CME 2 do konfiguracji i strojenia serwonapędów oraz napędów krokowych Copley Controls (m.in. Xenus, Accelnet, Stepnet, Accelus, Junus)
Źródło: dokumentacja producenta (Copley Controls CME 2 User Guide); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt

Set homing parameters and run optional homing tests. Perform the steps outlined below. 

1. image.pngScreenshot: Homing – On Main screen, click Home to open the Homing screenOn Main screen, click Home to open the Homing screen

image.pngScreenshot: Homing – On Main screen, click Home to open the Homing screen

22. Select the following homing parameters: 

image.pngHoming – parameters

ParameterDescription
Software limits: Positive / NegativePosition of user-defined travel limits that take effect after homing operation.
Software limits: Deceleration RateDeceleration rate used to stop a motor when approaching a software limit.
Software limits: DisableDisables the use of software limits by setting both limits to zero.
MethodHoming method. See Homing Methods.
Direction of MotionInitial direction of motion for the homing method (Pos or Neg).
Fast VelocityThe velocity used to find a limit or home switch. Also used when moving to an offset position, or a resolver or Servo Tube index position.
Slow VelocityThe velocity used to find a switch edge, incremental or analog encoder index pulse, or hard stop.
Accel/DecelThe acceleration and deceleration rate used during homing.
OffsetExecute a move of this distance after the reference is found. Set actual position to 0 and call the new position home.
Current LimitHard stop home is reached when the amplifier outputs the homing Current Limit continuously for the time specified in the Delay Time.
Current Delay TimeHard stop home is reached when the amplifier outputs the homing Current Limit continuously for the time specified in the Delay Time.
Following WarningShows the programmed following warning level.
Actual CurrentShows actual current being applied to windings during homing.
Actual PositionShows the actual position of the axis.

33. Optionally click Home to begin a homing sequence. To stop immediately, click Stop.
4

4. Click Save to save the settings to flash memory. Click Exit to close the screen

Słowa kluczowe

bazowanie, homing, limity programowe, metoda bazowania, prędkość bazowania, offset, home switch