5. Function Parameter List – Part 3 (PA–A0, U0)

Streszczenie: Tabela parametrów funkcyjnych KE300 (część 3 z 3): grupy PA–PP i A0 (PID, wobble, PLC, komunikacja, zarządzanie parametrami, moment) oraz tabela monitorowania U0 – zakresy nastaw, wartości fabryczne i możliwość zmiany.
EN: KE300 function parameter list (part 3 of 3): groups PA–PP and A0 (PID, wobble, PLC, communication, parameter management, torque) and the U0 monitoring table – setting ranges, factory defaults and modification attributes.

Dotyczy: falownik wektorowy Micno KE300 (zasilanie 1AC/3AC 220 V, 3AC 380 V, 3AC 660 V; moce 0,4–630 kW)
Źródło: dokumentacja producenta (Micno KE300 Series Inverter User Manual); tabele przepisane z obrazów na tekst – opracowanie Multiprojekt

Nawigacja: część 3 z 3 · poprzednia: ← poprzednia część (Part 2 (P5–P9))

5.1 Basic Function Parameter Table (Continued)

Kolumna „Modify” / Modify column: ○ – parameter can be modified in stop and running status; ◎ – cannot be modified in running status; ● – actual detected value, cannot be modified.

PA Group: PID Function

Function codeNameDetailed instructionFactory defaultModify
PA-00PID given source0: PA-01
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: Communication
6: Multi-step command
0○
PA-01PID given through keypad0.0 ~ PA-04 (PID given feedback range)0.0○
PA-02PID feedback source0: AI1
1: AI2
2: Keypad potentiometer
3: AI1 − AI2
4: High speed pulse HDI
5: Communication
6: AI1 + AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
0○
PA-03PID action direction0: Positive
1: Negative
0○
PA-04PID given feedback rangePA-01 (PID given through keypad) ~ 1000.0100.0○
PA-05Proportional gain Kp10.0 ~ 100.020.0○
PA-06Integration time Ti10.01s ~ 10.00s2.00s○
PA-07Differential time Td10.000s ~ 10.000s0.000s○
PA-08Cutoff frequency of PID reverse0.00 ~ P0-10 (maximum frequency)0.00Hz○
PA-09PID deviation limit0.0% ~ 100.0%0.0%○
PA-10PID differential amplitude0.00% ~ 100.00%0.10%○
PA-11PID given filter time0.00 ~ 650.00s0.00s○
PA-12PID feedback filter time0.00 ~ 60.00s0.00s○
PA-13PID output filter time0.00 ~ 60.00s0.00s○
PA-14Reserved––○
PA-15Proportional gain Kp20.0 ~ 100.020.0○
PA-16Integration time Ti20.01s ~ 10.00s2.00s○
PA-17Differential time Td20.000s ~ 10.000s0.000s○
PA-18PID parameter switching condition0: No switching
1: Switching via terminals
2: Automatic switching according to the deviation
0○
PA-19PID parameter switching deviation 10.0% ~ PA-2020.0%○
PA-20PID parameter switching deviation 2PA-19 ~ 100.0%80.0%○
PA-21PID initial value0.0% ~ 100.0% (printed in the source as “00.0%”)0.0%○
PA-22PID initial value holding time0.00 ~ 360.00s0.00s○
PA-23Forward maximum value between two output deviation0.00% ~ 100.00%1.00%○
PA-24Reverse maximum value between two output deviation0.00% ~ 100.00%1.00%○
PA-25PID integration attributeUnits place: integration separate
0: Invalid
1: Valid
Tens place: stop integrating or not after output reaches limit
0: Keep integrating
1: Stop integrating
00○
PA-26PID feedback lost detection value0.0%: no judgment for feedback lost
0.1% ~ 100.0%
0.0%○
PA-27PID feedback lost detection time0.0s ~ 20.0s0.0s○
PA-28PID stop calculation0: No calculation when stop
1: Calculation when stop
1○

Pb Group: Wobble Frequency, Fixed Length, Counting

Function codeNameDetailed instructionFactory defaultModify
Pb-00Wobble frequency setting mode0: Relative to center frequency
1: Relative to maximum frequency
0○
Pb-01Wobble frequency amplitude0.0% ~ 100.0%0.0%○
Pb-02Sudden jump frequency amplitude0.0% ~ 50.0%0.0%○
Pb-03Wobble frequency cycle0.1s ~ 3000.0s10.0s○
Pb-04Triangular wave rise time of wobble frequency0.1% ~ 100.0%50.0%○
Pb-05Setting length0m ~ 65535m1000m○
Pb-06Actual length0m ~ 65535m0m○
Pb-07Number of pulses per meter0.1 ~ 6553.5100.0○
Pb-08Setting count value1 ~ 655351000○
Pb-09Designated count value1 ~ 655351000○

PC Group: Multi-step Command and Simple PLC

Function codeNameDetailed instructionFactory defaultModify
PC-00Multi-step command 0-100.0% ~ 100.0%0.0%○
PC-01Multi-step command 1-100.0% ~ 100.0%0.0%○
PC-02Multi-step command 2-100.0% ~ 100.0%0.0%○
PC-03Multi-step command 3-100.0% ~ 100.0%0.0%○
PC-04Multi-step command 4-100.0% ~ 100.0%0.0%○
PC-05Multi-step command 5-100.0% ~ 100.0%0.0%○
PC-06Multi-step command 6-100.0% ~ 100.0%0.0%○
PC-07Multi-step command 7-100.0% ~ 100.0%0.0%○
PC-08Multi-step command 8-100.0% ~ 100.0%0.0%○
PC-09Multi-step command 9-100.0% ~ 100.0%0.0%○
PC-10Multi-step command 10-100.0% ~ 100.0%0.0%○
PC-11Multi-step command 11-100.0% ~ 100.0%0.0%○
PC-12Multi-step command 12-100.0% ~ 100.0%0.0%○
PC-13Multi-step command 13-100.0% ~ 100.0%0.0%○
PC-14Multi-step command 14-100.0% ~ 100.0%0.0%○
PC-15Multi-step command 15-100.0% ~ 100.0%0.0%○
PC-16Simple PLC running mode0: Stop after one cycle
1: Keep last frequency after one cycle
2: Circular running
0○
PC-17Simple PLC storage selection when power-downUnits place: storage selection when power-off
0: Not store
1: Store
Tens place: storage selection when stop
0: Not store
1: Store
00○
PC-18Phase 0 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-19Phase 0 ACC/DEC time selection0 ~ 30○
PC-20Phase 1 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-21Phase 1 ACC/DEC time selection0 ~ 30○
PC-22Phase 2 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-23Phase 2 ACC/DEC time selection0 ~ 30○
PC-24Phase 3 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-25Phase 3 ACC/DEC time selection0 ~ 30○
PC-26Phase 4 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-27Phase 4 ACC/DEC time selection0 ~ 30○
PC-28Phase 5 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-29Phase 5 ACC/DEC time selection0 ~ 30○
PC-30Phase 6 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-31Phase 6 ACC/DEC time selection0 ~ 30○
PC-32Phase 7 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-33Phase 7 ACC/DEC time selection0 ~ 30○
PC-34Phase 8 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-35Phase 8 ACC/DEC time selection0 ~ 30○
PC-36Phase 9 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-37Phase 9 ACC/DEC time selection0 ~ 30○
PC-38Phase 10 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-39Phase 10 ACC/DEC time selection0 ~ 30○
PC-40Phase 11 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-41Phase 11 ACC/DEC time selection0 ~ 30○
PC-42Phase 12 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-43Phase 12 ACC/DEC time selection0 ~ 30○
PC-44Phase 13 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-45Phase 13 ACC/DEC time selection0 ~ 30○
PC-46Phase 14 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-47Phase 14 ACC/DEC time selection0 ~ 30○
PC-48Phase 15 running time0.0s (m) ~ 6500.0s (m)0.0s (m)○
PC-49Phase 15 ACC/DEC time selection0 ~ 30○
PC-50Timing unit (simple PLC mode)0: s (second)
1: m (minute)
0○
PC-51Multi-step command 0 given mode0: PC-00
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: PID control
6: Keypad setting frequency (P0-08), can be modified via UP/DN
0○

Pd Group: Communication Parameters

Function codeNameDetailed instructionFactory defaultModify
Pd-00Baud rate0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
5○
Pd-01Data format0: No parity check (8-N-2)
1: Even parity check (8-E-1)
2: Odd parity check (8-O-1)
3: No parity check (8-N-1)
0○
Pd-02Local address1 ~ 247, 0 is broadcast address1○
Pd-03Response delay0ms ~ 20ms2○
Pd-04Communication timeout time0.0 (invalid)
0.1s ~ 60.0s
0.0○
Pd-05Communication protocol selection0: Non-standard MODBUS protocol
1: Standard MODBUS protocol
1○
Pd-06Communication read current resolution0: 0.01A
1: 0.1A
0○

PE Group: Reserved Function

Function codeNameDetailed instructionFactory defaultModify
FE-00 (PE-00)Reserved––○

PP Group: Function Code Management

Function codeNameDetailed instructionFactory defaultModify
PP-00User password0 ~ 655350○
PP-01Parameter initialization0: No action
1: Restore factory default, but not including motor parameters
2: Clear the record
0◎
PP-02Function parameter group display selectionUnits place: U0 group display selection
0: No display
1: Display
Tens place: A0 group display selection
0: No display
1: Display
00◎
PP-03Reserved––●
PP-04Function code modification attribute0: Disable
1: Enable
0○

A0 Group: Torque Control Parameters

Function codeNameDetailed instructionFactory defaultModify
A0-00Speed/torque control mode selection0: Speed control
1: Torque control
0◎
A0-01Torque setting source selection in torque control mode0: Keypad (A0-03)
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: Communication
6: Min (AI1, AI2)
7: Max (AI1, AI2)
0◎
A0-03Torque setting through keypad in torque control mode-200.0% ~ 200.0%150.0%○
A0-04Torque filter time0.00s ~ 10.00s0.00s○
A0-05Forward maximum frequency in torque control mode0.00Hz ~ P0-10 (maximum frequency)50.00Hz○
A0-06Reverse maximum frequency in torque control mode0.00Hz ~ P0-10 (maximum frequency)50.00Hz○
A0-07Acc time in torque control mode0.00s ~ 36000s0.00s○
A0-08Dec time in torque control mode0.00s ~ 36000s0.00s○

5.2 Monitoring Parameter Table

U0 Group: Basic Monitoring Parameters

Function codeNameMinimum unit
U0-00Running frequency (Hz)0.01Hz
U0-01Setting frequency (Hz)0.01Hz
U0-02DC bus voltage (V)0.1V
U0-03Output voltage (V)1V
U0-04Output current (A)0.01A
U0-05Output power (kW)0.1kW
U0-06Output torque (%)0.1%
U0-07DI input status1
U0-08DO output status1
U0-09AI1 voltage (V)0.01V
U0-10AI2 voltage (V)0.01V
U0-11Radiator temperature1 °C
U0-12Count value1
U0-13Length value1
U0-14Load speed1
U0-15PID setting1
U0-16PID feedback1
U0-17PLC phase1
U0-18HDI input pulse frequency (Hz)0.01kHz
U0-19Feedback speed (unit 0.1Hz)0.1Hz
U0-20Remain running time0.1 min
U0-21AI1 voltage before calibration0.001V
U0-22AI2 voltage before calibration0.001V
U0-23Keypad potentiometer voltage before calibration0.001V
U0-24Linear velocity1 m/min
U0-25Current power-on time1 min
U0-26Current running time0.1 min
U0-27HDI input pulse frequency1Hz
U0-28Communication setting value0.01%
U0-29Reserved0.01Hz
U0-30Main frequency A display0.01Hz
U0-31Auxiliary frequency B display0.01Hz
U0-32Reserved1
U0-33Reserved0.1°
U0-34Motor temperature1 °C
U0-35Target torque (%)0.1%
U0-36Reserved1
U0-37Power factor angle0.1°
U0-38Reserved1
U0-39Reserved1V
U0-40Reserved1V
U0-41DI input status visual display1
U0-42DO input status visual display1
U0-43DI function status display 1 (function 01 – function 40)1
U0-44DI function status visual display 2 (function 41 – function 80)1
U0-59Setting frequency (%)0.01%
U0-60Running frequency (%)0.01%
U0-61Inverter status1