6. Parameter Description – Part 3 (Group P4)

Streszczenie: Opis parametrów KE600 (część 3 z 8): zaciski wejściowe: funkcje DI 0–50 (D1–D10), sterowanie 2- i 3-przewodowe, krzywe AI, wejście impulsowe HDI, opóźnienia i logika DI.
EN: KE600 parameter description (part 3 of 8): input terminals: DI functions 0–50 (D1–D10), two-/three-wire control, AI curves, HDI pulse input, DI delays and logic.

Dotyczy: falownik wektorowy z zamkniętą pętlą Micno KE600 (zasilanie 3AC 220 V, 3AC 380 V, 3AC 660 V; moce 1,5–630 kW)
Źródło: dokumentacja producenta (Micno KE600 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt

Nawigacja: część 3 z 8 · poprzednia: ← Part 2 (Groups P1–P3) · następna: Part 4 (Groups P5–P6) →

Group P4 Input Terminal

The standard Inverter has 7 multifunctional digital input terminals (HDI can be used as high speed pulse input terminal) and two analog input terminals.

Digital input terminal functions

ParameterNameFactory default
P4-00D1 terminal function1
P4-01D2 terminal function2
P4-02D3 terminal function0
P4-03D4 terminal function0
P4-04D5 terminal function0
P4-05D6 terminal function0
P4-06D7/HDI terminal function0
P4-07D8 terminal function0
P4-08D9 terminal function0
P4-09D10 terminal function0

These parameters are used to set the functions of the multifunctional digital input terminals.

Note: D8, D9 and D10 are from the I/O extension card

Digital input (DI) terminal functions – setting values for P4-00 … P4-09

Setting valueFunctionDescription
0No functionThe no operation function can be set on the unused terminals so as to prevent error action.
1Forward (FWD)Control the inverter forward and reverse via the external terminals.
2Reverse (REV)Control the inverter forward and reverse via the external terminals.
3Three-line running controlThis terminal is used to confirm that the inverter running mode is three-line control mode. Refer to P4-11 (terminal command mode) for details.
4Forward Jog (FJOG)FJOG refers to Jog forward running, RJOG refers to Jog reverse running. Regarding Jog running frequency and Jog ACC/DEC time, please refer to F8-00, F8-01 and F8-02.
5Reverse Jog (RJOG)See Forward Jog (FJOG).
6Terminal UPWhen the frequency is given by the external terminals, it is used as increment and decrement commands of frequency modification. When the frequency source is set by digital, it can be used to adjust the setting frequency.
7Terminal DOWNSee Terminal UP.
8Coast to stopThe inverter locks the output, and the motor stop process is beyond the inverter control. This mode is the same as the meaning of coast-to-stop as described in P6-10.
9Fault reset (RESET)External fault reset function. It is the same as the function of RESET key on the keyboard. Using this function can realize long-distance fault reset.
10Pause runningThe inverter decelerates to stop, but all the running parameters are in the memory status, such as PLC parameter, wobble frequency parameter and PID parameter. After this signal disappears, the inverter restores to the status before stopping.
11External fault normally open inputAfter the signal is sent to the inverter, the inverter reports fault E-15 and acts according to the fault protection action mode (see P9-47).
12Multi-step speed terminal 1It can realize 16 steps or 16 other command settings through 16 statuses of the four terminals. See attached table 1.
13Multi-step speed terminal 2It can realize 16 steps or 16 other command settings through 16 statuses of the four terminals. See attached table 1.
14Multi-step speed terminal 3It can realize 16 steps or 16 other command settings through 16 statuses of the four terminals. See attached table 1.
15Multi-step speed terminal 4It can realize 16 steps or 16 other command settings through 16 statuses of the four terminals. See attached table 1.
16ACC/DEC time selection terminal 1It can select four types of ACC/DEC time through 4 statuses of the two terminals. See attached table 2.
17ACC/DEC time selection terminal 2It can select four types of ACC/DEC time through 4 statuses of the two terminals. See attached table 2.
18Main frequency source switchingUsed to switch different frequency source. According to the setting of frequency source selection (P0-07), when setting switching between two frequency sources is frequency source, it can achieve switching two frequency sources via this terminal.
19UP and DOWN setting clear (terminal and keyboard)When the frequency reference is digital frequency reference, this terminal can be used to clear the frequency value modified by UP/DOWN and thus restore the reference frequency to the setting value of P0-08.
20Running command switching terminalWhen the command source (P0-02) is set to 1, it performs switching between terminal control and keyboard control via this terminal. When the command source (P0-02) is set to 2, it performs switching between communication control and keyboard control via this terminal.
21ACC/DEC invalidProtect the inverter from being affected by the external signals (except stop command), and maintain the current frequency.
22PID pausePID is invalid temporarily, and the inverter maintains the current frequency output, no longer adjusts PID of frequency source.
23PLC status resetPLC pauses during the execution process. When it runs again, it can restore to the initial status of simple PLC via this terminal.
24Wobble frequency pauseThe inverter outputs the central frequency. Wobble frequency function pauses.
25Counter inputThe input terminal of counting pulse.
26Counter resetClear the counter status.
27Length count inputInput terminal of length counting.
28Length resetLength clear.
29Torque control invalidTorque control is invalid, the inverter adopts speed control mode.
30PULSE frequency input (only valid for HDI)HDI is pulse input terminal.
31ReservedReserved.
32DC braking commandWhen this terminal is valid, the inverter directly switches to DC braking status.
33External fault normally close inputAfter the external fault normally close signal is sent to the inverter, the inverter reports fault E-15 and stops.
34Frequency modification enabledIf this function is valid, the inverter does not respond to the frequency changing, until this terminal is invalid.
35PID action direction reverseWhen this terminal is valid, PID action direction is the opposite of value set by PA-03.
36External stop terminal 1The inverter can be stopped by this terminal under keypad control, which has the same function as STOP key.
37Control command switching terminal 2Used to switch between terminal control and communication control. If command source selection is set to terminal control, then the system switches to communication control when the terminal is valid, vice versa.
38PID integration stopWhen this terminal is valid, PID integration adjustment function will stop working, but PID ratio adjustment and differential adjustment functions are still valid.
39Switch frequency source A to preset frequencyWhen this terminal is valid, frequency source A is replaced by preset frequency (P0-08).
40Switch frequency source B to preset frequencyWhen this terminal is valid, frequency source B is replaced by preset frequency (P0-08).
41ReservedReserved.
42ReservedReserved.
43PID parameter switchingWhen PID parameter switching condition is DI terminal (PA-18=1) and this terminal is invalid, PID parameter is determined by PA-05 ~ PA-07. When this terminal is valid, PID parameter is determined by PA-15 ~ PA-17.
44Customized fault 1When customized fault 1 and 2 are valid, the inverter alarms E-27 and E-28, which would be processed according to the action mode set by P9-49.
45Customized fault 2See Customized fault 1.
46Speed control/torque control switchingMake the inverter switch between speed control and torque control mode. When this terminal is invalid, the inverter runs at the mode set by A0-00 (speed/torque control mode), the inverter switches to another mode when the terminal is valid.
47Emergency stopWhen the terminal is valid, the inverter stops with fastest speed; during the process, the current is as upper limits are set. This function is applied in the situation in which the inverter needs to stop ASAP when the system is in emergency status.
48External stop terminal 2In any control mode (keypad control, terminal control, communication control), the inverter can decelerate to stop via this terminal and the deceleration time is DEC time 4.
49Deceleration DC brakingWhen this terminal is valid, the inverter decelerates to the stop DC braking starting frequency, then switches to DC braking status.
50The running time resetWhen the terminal is valid, the inverter will clear the running time to zero; this function needs to be used together with timing running (P8-42) and running time arrival (P8-53).

Attached table 1 – multi-step command selection (K4…K1)

K4K3K2K1Command settingCorresponding parameter
OFFOFFOFFOFFMulti-step command 0PC-00
OFFOFFOFFONMulti-step command 1PC-01
OFFOFFONOFFMulti-step command 2PC-02
OFFOFFONONMulti-step command 3PC-03
OFFONOFFOFFMulti-step command 4PC-04
OFFONOFFONMulti-step command 5PC-05
OFFONONOFFMulti-step command 6PC-06
OFFONONONMulti-step command 7PC-07
ONOFFOFFOFFMulti-step command 8PC-08
ONOFFOFFONMulti-step command 9PC-09
ONOFFONOFFMulti-step command 10PC-10
ONOFFONONMulti-step command 11PC-11
ONONOFFOFFMulti-step command 12PC-12
ONONOFFONMulti-step command 13PC-13
ONONONOFFMulti-step command 14PC-14
ONONONONMulti-step command 15PC-15

When the frequency source selection is multi-step speed, 100% of PC-00~PC-15 correspond to P0-10 (maximum frequency).

Multi-step command not only can set as multi-step speed, but also can set as PID given source, to meet the requirement of need to switch between different given values.

Attached table 2 – ACC/DEC time selection

Terminal 2Terminal 1Acceleration or deceleration time selectionCorresponding parameters
OFFOFFACC time/DEC time 1P0-17, P0-18
OFFONACC time/DEC time 2P8-03, P8-04
ONOFFACC time/DEC time 3P8-05, P8-06
ONONACC time/DEC time 4P8-07, P8-08
ParameterNameFactory defaultSetting range
P4-10Terminal filter time0.010s0.000s ~ 1.000s

It is used to set the sensitivity of DI terminal. If the digital input terminal is vulnerable to interferences and may cause error action, it can increase this parameter value to enhance the anti-interference capability.

However, this operation will reduce the sensitivity of DI terminal.

ParameterNameFactory defaultSetting range
P4-11Terminal command mode00: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2

This parameter defines four different modes of controlling the operation of the inverter via the external terminals.

0: Two-line running mode 1: This is the most common mode. The forward/reverse rotation of the motor is decided by the commands of FWD and REV terminals.

Two-line mode 1 – terminal settings

TerminalSetting valueDescription
DIx1Forward running (FWD)
DIy2Reverse running (REV)

Figure 6-5 Two-line running mode 1 – logic

K1K2Running command
00Stop
01Reverse
10Forward
11Stop

Diagram description (text version): Switch K1 connects DIx (Forward, FWD) and switch K2 connects DIy (Reverse, REV) to COM (digital common terminal).

1: Two-line running mode 2: When this mode is adopted, REV is enabled terminal. The direction is determined by the status of FWD.

Two-line mode 2 – terminal settings

TerminalSetting valueDescription
DIx1Forward running (FWD)
DIy2Forward running (REV) – as in the source; in this mode DIy determines the running direction

Two-line running mode 2 – logic (figure captioned “Figure 6-6 Three-line Running Mode 2” in the source)

K1K2Running command
00Stop
01Stop
10Forward
11Reverse

Diagram description (text version): Switch K1 connects DIx (Forward, FWD) and switch K2 connects DIy (Reverse, REV) to COM (digital common terminal); K1 enables running and K2 selects the direction.

2: Three-line running mode 1: In this mode, DIn is enabled terminal, and the direction is controlled by FWD and REV respectively. However, the pulse is enabled through disconnecting the signal of DIn terminal when the inverter stops.

Three-line mode 1 – terminal settings

TerminalSetting valueDescription
DIx1Forward running (FWD)
DIy2Reverse running (REV)
DIn3Three-line running control

To make the inverter run, users must close DIn terminal firstly. It can achieve the motor forward or reverse control via pulse rising of DIx or DIy.

It can achieve the inverter stop via cutting off DIn terminal signal. DIx. DIy. DIn are DI1~DI6, HDI multifunctional input terminals, the valid input of DIx (DIy) is pulses signal, and the valid input of DIn is level signal.

Figure 6-7: Three-line running mode 1 wiring

Diagram description (text version): Figure 6-7 Three-line running mode 1: push button SB2 (normally open) connects DIx (Forward, FWD), push button SB1 (normally closed) connects DIn (three-line running control – stop) and push button SB3 (normally open) connects DIy (Reverse, REV) to COM (digital common terminal).

Where,

SB1: Stop button

SB2: Forward rotation button

SB3: Reverse rotation button

3: Three-line running mode 2: In this mode, DIn is enabled terminal, and the running command is given by FWD, while the direction is determined by the status of REV. Stop command is performed through disconnecting the DIn signal.

Three-line mode 2 – terminal settings

TerminalSetting valueDescription
DIx1Forward running (FWD)
DIy2Reverse running (REV)
DIn3Three-line running control

To make the inverter run, users must close DIn terminal firstly, and then the motor running signal will be generated by DIx pulse rising edge and the motor direction signal will be generated by Dy status.

It can achieve the inverter stop via cutting off DIn terminal signal. DIx. DIy. DIn are DI1~DI6, HDI multifunctional input terminals, the valid input of DIx is pulses signal, and the valid input of DIn (DIy) is level signal.

Figure 6-8 Three-line running mode 2 – direction switch K

KRunning direction
0Forward
1Reverse

Diagram description (text version): Push button SB2 (normally open) connects DIx (Forward, FWD – run command), push button SB1 (normally closed) connects DIn (three-line running control – stop/enable) and switch K connects DIy (Reverse, REV – direction) to COM (digital common terminal).

Where,

SB1: Stop button

SB2: Running button

ParameterNameFactory defaultSetting range
P4-12UP/DN change rate1.00Hz/s0.001Hz/s ~ 50.000Hz/s

Terminals UP/DOWN is used to adjust the change rate when setting frequency.

When P0-22 is set to 2, the range is 0.001~50.000Hz/s.

When P0-22 is set to 1, the range is 0.01~50.00Hz/s.

ParameterNameFactory defaultSetting range
P4-13AI curve 1 minimum input0.00V0.00V ~ P4-15
P4-14AI curve 1 minimum input corresponding setting0.0%-100.00% ~ 100.0%
P4-15AI curve 1 maximum input10.00VP4-13 ~ 10.00V
P4-16AI curve 1 maximum input corresponding setting100.0%-100.00% ~ 100.0%
P4-17AI1 filter time0.10s0.00s ~ 10.00s

The above function codes define the relationship between the analog input voltage and analog input setting value.

When the analog input voltage is bigger than P4-15 (maximum input of AI curve 1), then calculate the analog voltage according to maximum input. When the analog input voltage is smaller than P4-13 (minimum input of AI curve 1), then calculate the analog voltage with minimum input or 0.0% according to

P4-34 (AI below minimum input setting selection).

When the analog input is current input, 1mA current equals to 0.5V voltage.

AI1 input filter time is used to set AI1 software filter time, when the site analog signal can be easily disturbed, please increase filter time to stable the detected analog signal, but the bigger the filter time is, the slower the response speed of the analog detection is . So please set this parameter according to the situation.

In difference applications, 100% of analog input corresponds to different nominal values. Refer to all the application parts for details.

Several setting examples are shown in the following figures:

Chart: Figure 6-9 analog reference to setting (−100% … 100%)

Diagram description (text version): Analog reference to setting: the corresponding setting (frequency, torque) rises linearly from 0% at 0 V (0 mA) to 100% at 10 V (20 mA). Figure 6-9 Corresponding relationship between analog reference and setting: the corresponding setting (frequency, torque) rises linearly from −100% at 0 V (0 mA) to +100% at 10 V (20 mA), crossing 0% in the middle of the input range.

ParameterNameFactory defaultSetting range
P4-18AI curve 2 minimum input0.00V0.00V ~ P4-20
P4-19AI curve 2 minimum input corresponding setting0.0%-100.00% ~ 100.0%
P4-20AI curve 2 maximum input10.00VP4-18 ~ 10.00V
P4-21AI curve 2 maximum input corresponding setting100.0%-100.00% ~ 100.0%
P4-22AI2 filter time0.10s0.00s ~ 10.00s
ParameterNameFactory defaultSetting range
P4-23AI curve 3 minimum input0.00V-10.00V ~ P4-25
P4-24AI curve 3 minimum input corresponding setting0.0%-100.00% ~ 100.0%
P4-25AI curve 3 maximum input10.00VP4-23 ~ 10.00V
P4-26AI curve 3 maximum input corresponding setting100.0%-100.00% ~ 100.0%
P4-27Keypad potentiometer input filter time0.10s0.00s ~ 10.00s
P4-28HDI minimum input0.00kHz0.00kHz ~ P4-30
P4-29HDI minimum input corresponding setting0.0%-100.00% ~ 100.0%
P4-30HDI maximum input50.00kHzP4-28 ~ 100.00kHz
P4-31HDI maximum input setting100.0%-100.00% ~ 100.0%
P4-32HDI filter time0.10s0.00s ~ 10.00s

This group of function code defines the corresponding relationship when the pulse is used as frequency setting mode.

The pulse frequency input can only be input via HDI channel. The applications of this group function are similar as those of AI curve 1 function.

ParameterNameFactory defaultSetting range
P4-33AI curve selection321Units place – AI1 curve selection:
1: Curve 1 (see P4-13 ~ P4-16)
2: Curve 2 (see P4-18 ~ P4-21)
3: Curve 3 (see P4-23 ~ P4-26)
Tens place – AI2 curve selection, ibid.

Units place and tens place of this function code are used to select analog input AI1, AI2 corresponding setting curve.

Curve 1, curve 2, curve 3 are 2 points curves, set by P4 group.

Standard inverter has 2 analog input terminals.

ParameterNameFactory defaultSetting range
P4-34AI below minimum input setting selection000Units place – AI1 below minimum input setting selection:
0: Correspond to minimum input setting
1: 0.0%
Tens place – AI2 below minimum input setting selection (0 ~ 1, ibid.)
Hundreds place – keypad potentiometer below minimum input setting selection (0 ~ 1, ibid.)

The parameter is used to set how to confirm the analog corresponding setting when the analog input voltage is lower than the setting “the minimum input”.

Units place, tens place and hundreds place of this function code correspond to the analog input AI1, AI2 and Keypad potentiometer.

If the selection is 0, when AI input is lower than “the minimum input”, the analog value corresponding setting is the curve “the minimum input corresponding setting” (P4-14, P4-19, P4-24) determined by the function code.

If the selection is 1, when AI input is lower than “the minimum input”, the analog value corresponding setting is 0.0%.

ParameterNameFactory defaultSetting range
P4-35DI1 delay time0.0s0.0s ~ 3600.0s
P4-36DI2 delay time0.0s0.0s ~ 3600.0s
P4-37DI3 delay time0.0s0.0s ~ 3600.0s

Used to set the delay time when DI terminal status changing.

Currently only DI1, DI2, DI3 have setting delay time function.

ParameterNameFactory defaultSetting range
P4-38DI terminal valid mode selection 100000Units place – DI1 terminal valid status setting:
0: Active-high
1: Active-low
Tens place – D2 terminal valid status setting (0 ~ 1, ibid.)
Hundreds place – D3 terminal valid status setting (0 ~ 1, ibid.)
Thousands place – D4 terminal valid status setting (0 ~ 1, ibid.)
Ten thousands place – D5 terminal valid status setting (0 ~ 1, ibid.)
P4-39DI terminal active mode selection 200Units place – D6 terminal valid status setting:
0: Active-high
1: Active-low
Tens place – D7/HDI terminal valid status setting (0 ~ 1, ibid.)
Hundreds place – D8 terminal valid status setting (0 ~ 1, ibid.)
Thousands place – D9 terminal valid status setting (0 ~ 1, ibid.)
Ten thousands place – D10 terminal valid status setting (0 ~ 1, ibid.)

They are used to set the digital input terminal active status mode. If the selection is active-high, the relevant DI terminal connects with COM is valid, disconnect invalid. If the selection is active-high, the relevant DI terminal connects with COM is invalid, disconnect valid.