2.1 Product Inspection

Checking the following items when receiving the inverter

Confirmation itemsMethod
Confirm if the inverter is what you orderedCheck name plate
Damaged or notInspect the entire exterior of the inverter to see if there are any scratches or other damage resulting from shipping
Confirm if the fastening parts (screws, etc.) are loose or notCheck with a screwdriver if necessary
User’s manual, certification and other sparesUser’s manual and the relative spares

Please contact the local agent or our company directly if there is any damage on the inverter.

2.2 Model Description

Figure 2-1 Model description – example: KE600-5R5G-T4

Code segmentMeaningValues
KE600Close-loop vector control inverter series–
5R5Power rating5R5: 5.5 kW
GLoad typeG: constant torque type
T4Input voltageS2: 1AC 220–240V
T2: 3AC 220–240V
T4: 3AC 380–440V
T6: 3AC 660–690V

2.3 Description of Nameplate

Figure 2-2 Nameplate (example)

Nameplate fieldExample value
ManufacturerMICNO – Shenzhen Micno Electric Co., Ltd.
Model No. (MODEL)KE600-5R5G-T4
Power rating (POWER)5.5 kW
Input specification (INPUT)AC 3PH 380V ±15%, 50–60 Hz
Output specification (OUTPUT)13 A, AC 3PH 0–380 V, 0–300 Hz
Bar code010300051DC00004
MarkingCE 08204, Made in China

2.4 Selection Guide

Table 2-1 KE600 series inverter model and technical data

Inverter modelMotor (kW)Motor (HP)Rated input current (A)Rated output current (A)
3AC 220–240V ±15%
KE600-1R5G-T21.527.77
KE600-2R2G-T22.2310.59
KE600-004G-T24.0514.613
KE600-5R5G-T25.57.52625
KE600-7R5G-T27.5103532
KE600-011G-T2111546.545
KE600-015G-T2152062.560
KE600-018G-T218.5257675
KE600-022G-T222309291
KE600-030G-T23040113112
KE600-037G-T23750157150
KE600-045G-T24560180176
KE600-055G-T25575214210
KE600-075G-T275100307304
3AC 380–440V ±15%
KE600-1R5G-T41.525.03.8
KE600-2R2G-T42.236.86.0
KE600-004G-T44.05109
KE600-5R5G-T45.57.51513
KE600-7R5G-T47.5102017
KE600-011G-T411152625
KE600-015G-T415203532
KE600-018G-T418.5253837
KE600-022G-T422304645
KE600-030G-T430406260
KE600-037G-T437507675
KE600-045G-T445609290
KE600-055G-T45575112110
KE600-075G-T475100157150
KE600-090G-T490125180176
KE600-110G-T4110150214210
KE600-132G-T4132175256253
KE600-160G-T4160210307304
KE600-185G-T4185250350340
KE600-200G-T4200260385377
KE600-220G-T4220300430423
KE600-250G-T4250330468465
KE600-280G-T4280370525520
KE600-315G-T4315420590585
KE600-350G-T4350470665650
KE600-400G-T4400530785725
KE600-500G-T4500660880860
KE600-560G-T4560750980950
KE600-630G-T463084011301100
3AC 660–690V ±15%
KE600-015G-T615202119
KE600-018G-T618252822
KE600-022G-T622303528
KE600-030G-T637404035
KE600-037G-T637504745
KE600-045G-T645605552
KE600-055G-T655756563
KE600-075G-T6751009086
KE600-090G-T69010510098
KE600-110G-T6110130130121
KE600-132G-T6132175170150
KE600-160G-T6160210200175
KE600-185G-T6185250210195
KE600-200G-T6200260235215
KE600-220G-T6220300257245
KE600-250G-T6250330265260
KE600-280G-T6280370305300
KE600-315G-T6315420350330
KE600-350G-T6350470382374
KE600-400G-T6400530435410
KE600-450G-T6450600490465
KE600-500G-T6500660595550
KE600-630G-T6630840700680

Note: values as printed in the source; for KE600-030G-T6 the motor power column shows 37 kW (probably 30 kW), and KE600-004G-T4 is printed as “4.” kW.

2.5 Technical Specifications

Table 2-2 KE600 series inverter technical specifications

ItemTechnical indexSpecification
InputInput voltage3AC 220–240V ±15%, 3AC 380–440V ±15%, 3AC 660–690V ±15%
InputInput frequency47 ~ 63 Hz
OutputOutput voltage0 ~ rated input voltage
OutputOutput frequencyV/f control: 0 ~ 3000 Hz
Sensorless vector control: 0 ~ 300 Hz
Control featuresControl modeV/f control
Sensorless vector control (open-loop)
Close-loop vector control
Torque control
Control featuresOperation command modeKeypad control
Terminal control
Serial communication control
Control featuresFrequency setting modeDigital setting, analog setting, pulse frequency setting, serial communication setting, multi-step speed setting and simple PLC, PID setting, etc. These frequency settings can be combined and switched in various modes.
Control featuresOverload capacity150% 60 s, 180% 10 s, 200% 3 s
Control featuresStarting torque0 Hz/180% (close-loop vector control)
0.5 Hz/150% (SVC)
1 Hz/150% (V/f)
Control featuresSpeed adjustment range1:1000 (close-loop vector control)
1:100 (SVC)
1:50 (V/f)
Control featuresSpeed control precision±0.02% (close-loop vector control); ±0.5% (SVC)
Control featuresCarrier frequency1.0 ~ 16.0 kHz, automatically adjusted according to temperature and load characteristics
Control featuresFrequency accuracyDigital setting: 0.01 Hz
Analog setting: maximum frequency × 0.05%
Control featuresTorque boostAutomatic torque boost; manual torque boost: 0.1% ~ 30.0%
Control featuresV/f curveThree types: linear, multiple point and square type (1.2 power, 1.4 power, 1.6 power, 1.8 power, square)
Control featuresAcceleration/deceleration modeStraight line/S curve; four kinds of acceleration/deceleration time, range: 0.1 s ~ 3600.0 s
Control featuresDC brakingDC braking when starting and stopping
DC braking frequency: 0.0 Hz ~ maximum frequency, braking time: 0.0 s ~ 100.0 s
Control featuresJog operationJog operation frequency: 0.0 Hz ~ maximum frequency
Jog acceleration/deceleration time: 0.1 s ~ 3600.0 s
Control featuresSimple PLC and multi-step speed operationIt can realize a maximum of 16 segments speed running via the built-in PLC or control terminal.
Control featuresBuilt-in PIDBuilt-in PID control to easily realize the closed loop control of the process parameters (such as pressure, temperature, flow, etc.)
Control featuresAutomatic voltage regulationKeep output voltage constant automatically when input voltage fluctuates
Control functionCommon DC busCommon DC bus for several inverters, energy balanced automatically
Control functionTorque controlTorque control built-in
Control functionTorque limit“Rooter” characteristics, limit the torque automatically and prevent frequent over-current tripping during the running process
Control functionWobble frequency controlMultiple triangular-wave frequency control, special for textile
Control functionTiming/length/counting controlTiming/length/counting control function
Control functionOver-voltage and over-current stall controlLimit current and voltage automatically during the running process, prevent frequent over-current and over-voltage tripping
Control functionFault protection functionUp to 30 fault protections including over-current, over-voltage, under-voltage, overheating, default phase, overload, short circuit, etc.; can record the detailed running status during failure and has fault automatic reset function
Input/output terminalsInput terminalsProgrammable DI (digital input): 7 inputs, 1 is optional for high-speed pulse input, 3 can be extended
Programmable AI (analog input): AI1: 0 ~ 10 V or 0/4 ~ 20 mA; AI2: 0 ~ 10 V or 0/4 ~ 20 mA
Input/output terminalsOutput terminals1 programmable open collector output: 1 analog output (open collector output or high-speed pulse output), 2 can be extended
1 relay output, 1 can be extended
2 analog outputs: 0/4 ~ 20 mA or 0 ~ 10 V
Input/output terminalsCommunication terminalsRS485 communication interface, supports MODBUS-RTU communication protocol
Human machine interfaceLED displayDisplay frequency setting, output frequency, output voltage, output current, etc.
Human machine interfaceMultifunction keyQUICK/JOG key, can be used as multifunction key
EnvironmentAmbient temperature-10 °C ~ 40 °C, derated 4% when the temperature rises by every 1 °C (40 °C ~ 50 °C)
EnvironmentHumidity90% RH or less (non-condensing)
EnvironmentAltitude≤ 1000 m: output rated power; > 1000 m: output derated
EnvironmentStorage temperature-20 °C ~ 60 °C

2.6 External & Installation Dimensions

2.6.1 Parts Description

Diagram: KE600 parts (small frame)

Diagram description (text version): Parts of a small-frame KE600 inverter (isometric view): operation keypad on the front cover, cover installation hole, cable crossing (cable entry openings at the bottom) and inverter mounting holes.

Figure 2-3: KE600 parts (large frame, cover removed)

Diagram description (text version): Figure 2-3 Parts of inverter (large frame, front cover removed): inverter mounting holes and hoisting (lifting) holes at the top, keypad bracket, control board, and main circuit wiring terminals in two rows. The cabinet-type base below can have cable outlets at the front, back, left and right when installing in a cabinet.

2.6.2 External & Installation Dimensions

3AC 220–240V Inverter Dimension

Dimension drawing: 3AC 220V 1.5–15 kW inverters

Diagram description (text version): Front and side dimension drawings of 3AC 220–240V inverters: 1.5–4 kW (plastic housing with keypad, dimensions W, A, H, B, D) and 5.5–15 kW (metal housing with keypad, dimensions W, A, H1, H2, B, D). The values for each power range are given in the 3AC 220V dimension table.

Dimension drawing: 3AC 220V 18.5–75 kW inverters

Diagram description (text version): Front and side dimension drawing of 3AC 220–240V 18.5–75 kW inverters (cabinet with three mounting holes at the top): width W, mounting spacing A, heights H1, H2, B and depth D – values in the table below.

3AC 220V inverter dimensions

Power rangeW (mm)H1 (mm)H2 (mm)D (mm)A (mm)B (mm)Mounting bolt model
1.5 ~ 4 kW135240240173122.6229M4
5.5 kW17031428516790301.6M4
7.5 kW200329.1300177.290316.6M4
11 ~ 15 kW255439.6402.4209.6140423.6M5
18.5 ~ 22 kW280570521.2258190552M6
30 ~ 37 kW320600552330230582M8
45 ~ 55 kW320715662330230695.5M8
75 kW480790725385360768M10

W, H1, H2, D – external dimensions; A, B – installation dimensions.

For 1.5–4 kW the source gives a single height of 240 mm (H1 = H2).

3AC 380–440V Inverter Dimension

Dimension drawing: 3AC 380V 1.5–5.5 kW inverters

Diagram description (text version): Front and side dimension drawing of 3AC 380–440V 1.5–5.5 kW inverters (plastic housing with keypad): width W, mounting spacing A, height H, mounting spacing B and depth D – values in the 3AC 380V dimension table.

Dimension drawing: 3AC 380V 7.5–30 kW inverters

Diagram description (text version): Front and side dimension drawing of 3AC 380–440V 7.5–30 kW inverters (metal housing with keypad, two top mounting holes): width W, mounting spacing A, heights H1, H2, B and depth D – values in the 3AC 380V dimension table.

Dimension drawing: 3AC 380V 37–200 kW inverters

Diagram description (text version): Front and side dimension drawing of 3AC 380V 37–200 kW inverters (including 90–200 kW standard version, wall-mounted metal cabinet with three top mounting holes): width W, mounting spacing A, heights H1, H2, B and depth D – values in the 3AC 380V dimension table.

Dimension drawing: 3AC 380V 90–200 kW with base

Diagram description (text version): Front and side dimension drawing of the 90–200 kW non-standard inverter version with a floor base (ventilated base under the cabinet, lifting eyes at the top): width W, heights H1 (with base) and H2 (cabinet), depth D – values in the 3AC 380V dimension table.

3AC 380V inverter dimensions (1.5–200 kW)

Power rangeW (mm)H1 (mm)H2 (mm)D (mm)A (mm)B (mm)Mounting bolt model
1.5 ~ 5.5 kW135240240173122.6229M4
7.5 kW17031428516790301.6M4
11 ~ 15 kW200329.1300177.290316.6M4
18.5 kW225397.6365185.2120384.1M5
22 ~ 30 kW255439.6402.4209.6140423.6M5
37 ~ 45 kW280570521.2258190552M6
55 ~ 75 kW320600552330230582M8
90 ~ 110 kW (without base)320715662330230695.5M8
90 ~ 110 kW (with base)320992962330–––
132 ~ 200 kW (without base)480790725385360768M10
132 ~ 200 kW (with base)48011651125385–––

W, H1, H2, D – external dimensions; A, B – installation dimensions.

For 1.5–5.5 kW the source gives a single height (H1 = H2).

Note: Base is optional for 90–200 kW inverters. Standard inverters are without base.

Dimension drawing: 3AC 380V 220–630 kW without base

Diagram description (text version): Front and side dimension drawing of 3AC 380V 220–630 kW inverters without base (large cabinet with four top mounting holes): width W, mounting spacings A1 and A2, heights H1, H2, B and depth D – values in the table for 220–630 kW.

Dimension drawing: 3AC 380V 220–630 kW with base

Diagram description (text version): Front and side dimension drawing of 3AC 380V 220–630 kW inverters with floor base (ventilated base under the cabinet): width W, heights H1 and H2, depth D – values in the table below.

3AC 380V inverter dimensions (220–630 kW)

Power rangeW (mm)H1 (mm)H2 (mm)D (mm)A1 (mm)A2 (mm)B (mm)Mounting bolt model
220 ~ 315 kW (without base)700970900408160480946M10
220 ~ 315 kW (with base)70013901350408––––
350 ~ 630 kW (without base)940114011004582406601146M10
350 ~ 630 kW (with base)94016901650458––––

W, H1, H2, D – external dimensions; A1, A2, B – installation dimensions.

3AC 660–690V Inverter Dimension

Dimension drawing: 3AC 660V 15–160 kW without base

Diagram description (text version): Front and side dimension drawing of 3AC 660V 15–160 kW inverters without base (wall-mounted cabinet with three top mounting holes): width W, mounting spacing A, heights H1, H2, B and depth D – values in the 3AC 660V dimension table.

Dimension drawing: 3AC 660V 110–160 kW with base

Diagram description (text version): Front and side dimension drawing of 3AC 660V 110–160 kW inverters with the optional floor base: width W, heights H1 (with base) and H2 (cabinet), depth D – values in the table below.

3AC 660V inverter dimensions

Power rangeW (mm)H1 (mm)H2 (mm)D (mm)A (mm)B (mm)Mounting bolt model
15 ~ 37 kW (without base)280650601333290631.5M6
45 ~ 90 kW (without base)320808754356230780M8
110 ~ 160 kW (without base)480790725385360768M10
110 ~ 160 kW (with base)48011651125385–––

W, H1, H2, D – external dimensions; A, B – installation dimensions.

Dimension drawing: 3AC 660V 185–630 kW without base

Diagram description (text version): Front and side dimension drawing of 3AC 660–690V 185–630 kW inverters without base (double-door cabinet, four top mounting holes): width W, mounting spacings A1 and A2, heights H1, H2, B and depth D – values in the table below.

Dimension drawing: 3AC 660V 185–630 kW with base

Diagram description (text version): Front and side dimension drawing of 3AC 660V 185–630 kW inverters with floor base (double-door cabinet, four top mounting holes): width W, heights H1 and H2, depth D – values in the table below.

3AC 660V inverter dimensions (185–630 kW)

Power rangeW (mm)H1 (mm)H2 (mm)D (mm)A1 (mm)A2 (mm)B (mm)Mounting bolt model
185 ~ 250 kW (without base)700970900408160480946M10
185 ~ 250 kW (with base)70013901350408––––
280 ~ 630 kW (without base)940114011004582406601146M10
280 ~ 630 kW (with base)94016901650458––––

W, H1, H2, D – external dimensions; A1, A2, B – installation dimensions.

2.6.3 Keypad External Dimension

Dimension drawing: KE600 keypad (65 × 100 mm)

Diagram description (text version): Keypad dimension of KE600 inverters: front view 65 mm wide × 100 mm high (LED display, status LEDs, potentiometer knob and 8 keys), side view depth 27.4 mm, of which 15 mm is the front part.

Illustration: This keypad can be connected with the inverter externally by ordinary network cable, and it needs an additional bracket to fix it.

Dimension drawing: 65 × 100 mm keypad bracket and cut-out

Diagram description (text version): Left: 65×100 mm keypad bracket dimension – 73.3 mm wide × 108.3 mm high, depth 16.6 mm. Right: panel hole (cut-out) dimension for the keypad bracket – 69.5 mm wide × 104.5 mm high.

2.7 Routine Maintenance of Inverter

2.7.1 Routine Maintenance

The influence of the ambient temperature, humidity, dust and vibration will cause the aging of the devices in the inverter, which may cause potential fault of the inverter or reduce the service life of the inverter.

Therefore, it is necessary to carry out routine and periodical maintenance on the inverter.

Routine inspection Items include:

  1. Whether there is any abnormal change in the running sound of the motor;
  2. Whether the motor has vibration during the running;
  3. Whether there is any change to the installation environment of the inverter;
  4. Whether the inverter cooling fan works normally;
  5. Whether the inverter has over temperature.

Routine cleaning:

  1. The inverter should be kept clean all the time.
  2. The dust on the surface of the inverter should be effectively removed, so as to prevent the dust entering the inverter. Especially the metal dust is not allowed.
  3. The oil stain on the inverter cooling fan should be effectively removed.

2.7.2 Periodic Inspection

Please perform periodic inspection on the places where the inspection is a difficult thing.

Periodic inspection Items include:

  1. Check and clean the air duct periodically;
  2. Check if the screws are loose;
  3. Check if the inverter is corroded;
  4. Check if the wire connector has arc signs;
  5. Main circuit insulation test.

Remainder: When using the megameter (DC 500V megameter recommended) to measure the insulating resistance, the main circuit should be disconnected with the inverter. Do not use the insulating resistance meter to test the insulation of control circuit. It is not necessary to conduct the high voltage test (which has been completed upon delivery).

2.7.3 Replacement of Vulnerable Parts for Inverter

The vulnerable parts of the inverter include cooling fan and filter electrolytic capacitor, whose service life depends on the operating environment and maintenance status. General service life is shown as follows:

Part nameService life
Fan2 ~ 3 years
Electrolytic capacitor4 ~ 5 years

The user can determine the year of replacement according to the operating time.

1) Cooling fan

Possible reason for damage: Bearing is worn and blade is aging.

Judging criteria: Whether there is crack on the blade and whether there is abnormal vibration noise upon startup.

2) Filter electrolytic capacitor

Possible reason for damage: Input power supply in poor quality, high ambient temperature, frequent load jumping, and electrolyte aging.

Judging criteria: Whether there is liquid leakage and whether the safe valve has projected, and measure the static capacitance, and the insulating resistance.

2.7.4 Storage of Inverter

Upon acquiring the inverter, the user should pay attention to the following points regarding the temporary and long-term storage of the inverter:

  1. Pack the inverter with original package and place back into the packing box of our company.
  2. Long-term storage will degrade the electrolytic capacitor. Thus, the product should be powered up once every 2 years, each time lasting at least five hours. The input voltage should be increased slowly to the rated value with the regulator.

2.8 Instructions on Warranty of Inverter

Free warranty only applies to the inverter itself.

  1. MICNO provides 18 month warranty (starting from the date of original shipment as indicated on the barcode) for the failure or damage under normal use conditions. If the equipment has been used for over 18 months, reasonable repair expenses will be charged.
  2. Reasonable repair expenses will be charged for the following situations within 18 months:

a) The equipment is damaged because the user fails to comply with the requirements of the user’s manual;

b) Damage caused by fire, flood and abnormal voltage;

3) Damage caused when the inverter is used for abnormal function.

The service expenses will be calculated according to the standard of the manufacturer. If there is any agreement, the agreement should prevail.

Słowa kluczowe

Micno KE600, oznaczenie modelu, model code, tabliczka znamionowa, nameplate, prąd znamionowy, rated current, specyfikacja techniczna, technical specifications, wymiary, dimensions, panel, keypad, konserwacja, maintenance, gwarancja, warranty