4. Operation and Display

Streszczenie: Obsługa panelu KE600: przyciski i wskaźniki, menu trzypoziomowe i zmiana parametrów, stany pracy, hasło oraz autotuning parametrów silnika.
EN: KE600 keypad operation: keys and indicators, three-level menu and parameter editing, operating states, password and motor parameter autotuning.

Dotyczy: falownik wektorowy z zamkniętą pętlą Micno KE600 (zasilanie 3AC 220 V, 3AC 380 V, 3AC 660 V; moce 1,5–630 kW)
Źródło: dokumentacja producenta (Micno KE600 Series Inverter User Manual); tabele przepisane z obrazów na tekst, opisy rysunków – opracowanie Multiprojekt

4.1 Keypad Description

With the operation keypad, it can perform such operations on the inverter as function parameter modification, working status monitor and running control (start and stop).

Figure 4-1: Operation keypad diagram

Diagram description (text version): Figure 4-1 Operation keypad diagram: top row of function indicator lights RUN, FWD/REV, LOCAL/REMOT, TUNE/TRIP; 5-digit digital display (e.g. 50.00) with unit indicator lights Hz/RPM, A/% and V on the right; potentiometer knob. Keys: PRG/ESC (program/escape), DATA/ENTER (data enter), QUICK/JOG (shortcut key), ▲/▼ (digital modify keys), SHIFT (shift key), RUN (run key), STOP/RST (stop / fault reset key).

Function Key Description

Function indicatorDescription
RUNOff: stop status
On: operating status
FWD/REVOff: forward operation
On: reverse operation
LOCAL/REMOTOff: keypad control
Flashing: communication control
On: terminal control
TUNE/TRIPOn: torque control
Flashing slowly: parameter autotuning status
Flashing quickly: fault status

Unit Indicator Light Description

Unit indicatorDescription
HzFrequency unit
ACurrent unit
VVoltage unit
RPMRotation speed unit
%Percentage

Digital Display Zone

Five-number digit LED display, can display setting frequency, output frequency, various monitoring data and alarm code.

Keypad Button Description

ButtonNameFunction
PRG/ESCProgramming keyEntry and exit of primary menu
DATA/ENTERConfirmation keyProgressively enter menu, and confirm parameters
▲ (up)Increment keyProgressively increase data or function codes
▼ (down)Decrement keyProgressively decrease data or function codes
▷ (SHIFT)Shift keySelect the displayed parameters in turn on the stop display interface and running display interface, and select the modification bit of parameters when modifying parameters.
RUNRunning keyStart to run inverter under keyboard control mode
STOP/RSTStop/resetStop inverter in running status and reset operation in fault alarm status. The button’s characteristics are restricted by function code P7-02.
QUICK/JOGMulti-function selection keyFunction switching selection according to P7-01.

4.2 Function Code Checking and Modification Methods Description

The operation keypad of the KE600 Series Inverter adopts three-level menu structure to carry out operations such as parameter setting.

The three-level menu includes function parameter group (level 1 menu) → Function code (level 2 menu) → Function code setting value (level 3 menu). Refer to Figure 4-2 for the operation procedure.

Figure 4-2: Three-level menu operation procedure

Diagram description (text version): Figure 4-2 Operation procedure of three-level menu: from the zero-level menu (status display, e.g. 50.00) press PRG to enter the first-level menu (parameter group, e.g. P0, changed with ▲/▼); ENTER opens the second-level menu (function code, e.g. P0-08, changed with ▲/▼); ENTER opens the third-level menu (setting value, e.g. 30.00, changed with ▲/▼). PRG returns one level up at each step.

Description: When operating on level 3 menu, press PRG key or ENTER key to return to level 2 menu. The difference between PRG key and ENTER key is described as follows: Pressing ENTER KEY will save the setup parameter and return to the level 2 menu and then automatically shift to the next function code, while pressing PRG key will directly return to level 2 menu without saving the parameter, and it will return to the current function code.

Example: Modify the function code P3-02 from 10.00Hz to 15.00Hz. (The bold-type word indicates the flashing bit.)

Diagram: example of changing P3-02 to 15.00

Diagram description (text version): Example of parameter setting (P3-02 from 10.00 Hz to 15.00 Hz): 50.00 → PRG → P0 → ▲ to P3 → ENTER → P3.00 → ▲ to P3-02 → ENTER → value 010.00 → SHIFT ▷ to move the editing digit → ▲ to change the digit to 015.00 → PRG (save) → display P3-03 → PRG → P3 → PRG → back to 50.00.

In level 3 menu, if there is no flashing bit, it indicates that the function code cannot be modified. The possible reasons include:

  1. The function code is an unchangeable parameter, such as actual detection parameter, running record parameter, etc.
  2. The function code cannot be modified in running status. It can be modified only after the unit is stopped.

4.3 Power-on Initialization

Firstly the system initializes during the inverter power-on, and LED displays “8.8.8.8.8.8”. After initialization, the inverter is in fault protection status if a fault happens, or the inverter is in stand-by status

4.4 Fault Protection

In fault status, inverter will display fault code & record output current, output voltage, etc. For details, please refer to P9 (fault and protection) parameter group. Fault can be reset via STOP/RST key or external terminals.

4.5 Stand by

In stop or stand by status, parameters of multi-status can be displayed. Whether or not to display this parameter can be chosen through function code P7-05 (Stop status display parameter) according to binary bits.

In stop status, there are thirteen parameters can be chosen to display or not. They are: setting frequency, bus voltage, DI input status, DO output status, analog input AI1 voltage, analog input Al2 voltage, radiator temperature, count value, actual length, PLC running step, load speed display, PID setting, HDI input pulse frequency. The displaying of the chosen parameters can be switched in sequence by pressing “▷ (SHIFT)” button. Power on after power-off, the displayed parameters would be default considered as the chosen parameters before power-off.

4.6 Running

In running status, there are thirty two parameters can be chosen to display or not through function code P7-04 (running status display parameter 2) according to binary bits. They are: running frequency, setting frequency, DC bus voltage, output voltage, output current, output torque, DI input status, DO output status, analog input AI1 voltage, analog input AI2 voltage, radiator temperature, actual count value, actual length, line speed, PID setting, PID feedback, etc. The displaying of the chosen parameters can be switched in sequence by pressing “▷ (SHIFT)” button.

4.7 Password Setting

The inverter provides user password protection function. When PP-00 is set to non-zero value, it indicates the user password, and the password protection turns valid after exiting the function code editing status.

When pressing PRG key again, “------“will be displayed, and common menu cannot be entered until user password is input correctly.

To cancel the password protection function, enter with password and set PP-00 to “0”.

4.8 Motor Parameters Autotuning

To select the vector control running mode, it must input the nameplate parameter of the motor accurately prior to the running of the inverter. The Inverter will select standard motor parameters matching the nameplate parameter. Since the vector control mode relies highly on the motor parameters, it must acquire the accurate parameters of the controlled motor to ensure the good control performance.

The procedures for the automatic tuning of motor parameters are described below:

First, select the command source (P0-02) as the command channel of the operation keypad. Second, input the following parameters in accordance with the actual motor parameters:

P1-01 (A2-01): Rated motor power

P1-02 (A2-02): Rated motor voltage

P1-03 (A2-03): Rated motor current

P1-04 (A2-04): Rated motor frequency

P1-05 (A2-05): Rated rotation speed of motor

If the motor is completely disconnected from the load, set P1.11 (A2-11) to “2” (complete tuning), and press RUN key on the keyboard keypad, then the inverter will automatically calculate the following parameters:

P1-06 (A2-06): Stator resistance

P1-07 (A2-07): Rotor resistance

P1-08 (A2-08): Leakage inductance

P1-09 (A2-09): Mutual inductance

P1-10 (A2-10): Current without load

Finally, complete the automatic tuning of motor parameters.

If the motor cannot be completely disconnected with the load, set P1-11(A2-11) to “1” (static tuning), and then press RUN key on the keyboard panel.

The following motor parameters can be calculated automatically:

P1-06 (A2-06): Stator resistance

P1-07 (A2-07): Rotor resistance

P1-08 (A2-08): Leakage inductive reactance

Słowa kluczowe

Micno KE600, panel, keypad, PRG/ESC, DATA/ENTER, QUICK/JOG, menu trzypoziomowe, three-level menu, wyświetlacz, display, hasło, password, autotuning, P1-11